1.Check all trunkings are properly covered 检查所有线槽都全封盖 2. Check cable entry to box is wellterminated 检查进入配电箱的电览收尾良好 3. Check all wall openings are fully sealedwith fire resistance materials 检查过墙洞囗填塞以防火材料 4.Check floor openings is fully sealed withfire resistance materials 检查地面洞囗填充以防火材料 5.Check all cables are correctly tied toladder 检查所有电览正确地扣在览架上 6.Check all distribution boxes top port areproperly sealed 检查配电箱上方开口适当密封 7.Check all electrical boxes are correctlyearthed 检查配电箱正确地 8.Check earth bar inside ditribution boxsufficient for all earth lines 检查配电箱接地桥尺寸足够供所有地线 9.Check all earth lines inside distributionboxes are tightly secured 检查配电箱接地线在接桥己旋紧 10.Check all circuit breakers wiring areproper termination and tightly secured 检查所有空开的电线已旋紧及良好收尾 11.Check circuit breakers tripping current arecorrectly set 检查各接触器跳闸保护设置正确 12.Check cable number marking is wrappedfor all cabling 检查线览标签套在线缆上 13.Check colour marking is correctly markedon cables 检查电缆上的相位颜色标签正确 14.Circuit breaker box is securely earthed 检查接触器盒接地旋紧 15.All cables are clearely labelled &inlined with room no. 所有电线标号与房号相符 16.Check BMS lighting control box isproperly set up. 检查楼宇自控灯光控制箱设置适当 17.Check room lighting is provided andworkable 检查房内已提供照度灯及可以工作 18.Check fire detector is provided 检查消防检测器己安装 19.Check switch room door is of fire ratedtype 检查电制门为耐火门等级 20 Check room door lock for functioning 检查门锁工作正常 平台! |
|