配色: 字号:
阿法拉伐分油机EPC60
2023-06-27 | 阅:  转:  |  分享 
  
EPC 60

Service Engineer Training

Printed

Book No.

Mar 2008

EPS006 V 1

ight to make changes at any time without

possible errors and omissions or

this publication would be

be ordered from your local

a Laval Tumba AB

rts & Service

47 80 Tumba

eden

umba AB 2006.

Alfa Laval reserves the r

prior notice.

Any comments regarding

suggestions for improvement of

gratefully appreciated.

Copies of this publication can

Alfa Laval company.

Published by: Alf

Pa

SE - 1

Sw

? Copyright Alfa Laval T

Contents

1 The new marine control

system....................................... 1

2 Control cabinets...................................3

2.1 Introduction .......................................3

2.2 Cabinet with starter ........................4

2.2.1 Cabinet with starters...............................5

2.2.2 Contactor................................................6

2.2.3 AC/DC converter ....................................7

2.3 Heater cabinet ..................................9

2.3.1 Inside the cabinet.................................10

3 CPU and I/O...........................................13

3.1 Inside the cabinets........................13

3.1.1 I/O A3; digital input. .............................15

3.1.2 I/O A4; relay output...............................16

3.1.3 I/O A5; 6 relay output............................17

3.1.4 I/O A6; 4 relay output............................18

3.1.5 I/O A7; 4 Analogue input ......................19

3.1.6 I/O A8; 2 Analogue input ......................20

3.1.7 I/O A9; 2 relay output ...........................21

3.1.8 I/O A10; 4 input namur .........................22

3.1.9 I/O A11; 1 analogue input ....................23

3.1.10 I/O A14; 6 digital output .......................24

3.1.11 I/O A15; 2 digital input..........................25

3.1.12 I/O A12; 6 relay output .........................26

3.1.13 I/O A13; 6 digital input..........................27

3.2 CPU .....................................................28

3.2.1 Bus holder ............................................28

3.2.2 Terminal blocks.....................................29

3.3 The I/O boards .................................30

3.3.1 Change the I/O .....................................30

3.4 Programmable Inputs and

Outputs ..............................................31

3.4.1 Inputs ( I/O A13) ...................................31

3.4.2 Outputs (I/O A12) .................................31

3.5 I/O Test Function............................32

4 Operator Panel ...................................37

4.0.1 Buttons .................................................38

4.1 EPC 60 Menus..................................40

EPS006

4.2 Operation page ...............................41

4.3 Settings page ..................................41

4.3.1 Parameters ...........................................42

4.3.2 Time setting ......................................... 42

4.3.3 Operation info ...................................... 43

4.3.4 I/O Test ................................................ 45

4.3.5 Alarm history........................................ 46

4.3.6 System info .......................................... 48

4.3.7 IP settings ............................................ 48

4.3.8 Password/ Log in ................................. 49

4.4 Alarms List ...................................... 50

4.4.1 Alarm denomination............................. 51

4.4.2 Alarms on the EPC 60.......................... 52

5 Parameters............................................61

5.1 Setting List ..................................... 61

5.2 Additional parameter info........... 69

5.2.1 P & I setting P123 and 124 .................. 69

5.2.2 Calculating Operating Pressure .......... 70

5.2.3 Remote control/ monitoring ................. 71

5.2.4 Programmable in- and outputs............ 72

5.2.5 Cross connection/serial operation....... 72

5.3 ALCAP ............................................... 73

5.3.1 Testing the MT60 ................................. 74

6 Computer connection ....................75

6.1 Computer settup............................ 75

6.2 Download of application

software ........................................... 77

7 Servcom ..................................................79

7.0.1 Process view........................................ 80

7.0.2 Initial settup ......................................... 80

7.0.3 Connect to EPC60 ............................... 81

7.0.4 Parameter view .................................... 81

7.0.5 Managing parameters ......................... 82

7.0.6 Reports ................................................ 84

7.0.7 Logging ............................................... 88

8 Operating instructions..................91

8.1 Before First Startup...................... 91

8.2 Manual Start from Standstill ..... 93

8.3 Automatic Start from

Standstill ........................................ 100

8.4 During separation........................ 101

8.5 Stop.................................................. 103

8.5.1 CIP Start ............................................ 105

8.6 Heater Control (optional).......... 110

8.6.1 Control of the electric heater

(optional)............................................ 111

EPS006

8.6.2 Control of the CBM heater

(optional) ............................................113

8.6.3 If heater not controlled or external .....113

8.6.4 Heater shut down ...............................114

8.7 Operation without all sensors

(Emergency operation)...............115

8.7.1 System Without Speed Sensor ...........115

8.7.2 System Without Vibration Sensor........115

8.7.3 System Without Cover Switch.............115

8.7.4 System With PT1 Disabled .................116

8.7.5 System With PT4 Disabled .................116

8.7.6 System With PT5 Disabled

(S-separator only)...............................116

8.7.7 Control of Sludge Pump,

Level in Sludge Tank,

and Butterfly Valve..............................117

8.7.8 System Without Feed Pump ...............118

8.7.9 System Without Water Transducer

(S-separator only)...............................118

EPS006

EPS006

EPC 60 SERVICE ENGINEER TRAINING 1 THE NEW MARINE CONTROL SYSTEM

ol system1 The new marine contr

In 2003 it was decided that the EPC50 needs to

be replaced by another system.

The arguments for this decision were:

? High product care costs, as the EPC50 is an

Alfa Laval owned product

? Problems with component supply, EPC50 is

an old design, and so are many of its

components

? High product cost

? Too many claims

? Low flexibility

After an initial benchmark of many systems, one

supplier was chosen, B&R Automation, which is

a company located in Austria.

B&R Automation only work with OEM-

customers, which makes their product strategy

suitable for Alfa Laval.

In 2007 B&R Automation where selected to be

Alfa Laval’s preferred supplier for Automation

systems.

The development of EPC60 then began, and from

2004 the system has been developed and tested.

The first product to use the EPC60 will be the

Flex Range, with the first deliveries in June

2008.

Other marine systems will soon follow; projects

for new versions of Ecostream and FCM are

already started.

Also other, non-marine product will use the

EPC60 as a base for their automation.

EPS006 1

1 THE NEW MARINE CONTROL SYSTEM EPC 60 SERVICE ENGINEER TRAINING

2 EPS006

EPC 60 SERVICE ENGINEER TRAINING 2 CONTROL CABINETS

2 Control cabinets

2.1 Introduction

We have two types of cabinets; one with starters,

the large cabinet and one without starters, the

small cabinet. The small cabinet is intended for

customers that uses their own starters. Both

options are available for modules and lose

components.

The new cabinets are not integrated in the

module as on the S units. In the Flex modules we

are using standard cabinets mounted on the

module frames.

There are some new components in the cabinets

and we will go through them in this chapter.

Fig 2.1 Starter cabinet w/contactors and without

EPS006 3

2 CONTROL CABINETS EPC 60 SERVICE ENGINEER TRAINING

Q5 Q7 Q4

Q3/K3

Q1

T A 1

Q2/K2

X3 X4

X5-X20

Q1

X

0

24

90

1A

M

o

tor

s

t

ar

ter

Amm

e

ter

k

i

t

Ex

tr

a I/O

bo

ar

d

ter

m

i

nal

(

o

ptio

nal

)

Vi

br

atio

n tr

an

smi

tter

ter

m

inal

(

o

ptio

nal

)

Sp

eed t

r

a

n

sm

itte

r

t

e

r

m

in

al

(

opti

onal

)

S

t

eam

hea

ter

ter

m

i

nal

(

o

pt

i

o

na

l

)

Heat

tr

aci

ng t

e

r

m

in

al



(

opti

onal

)

E

l

e

c

tr

i

c

al

he

ater

ter

m

i

nal

(

o

pt

i

o

na

l

)

Em

er

g

enc

y s

t

op



Ci

r

c

ui

t br

eak

e

r

Ci

r

c

ui

t br

eak

e

r

Ci

r

c

uit

br

eak

er

2.2 Cabinet with starter

K 2 0

K 1 1 2

TR1

X401 X400 X501 X500

X1 X2

A9-A15

K 6

K 7

Q 6

OP1

P1

G A 1

Fr

on

t view

Inter

nal

vi

ew

Co

v

e

r

i

n

ter

l

oc

k

k

i

t

(

o

ptio

nal

)

ES

D

ki

t

(

o

pti

onal

)

PL

C



A1

-A

8

Sl

ot

s

Fa n

H

e

at

t

r

a

c

i

n

g k

i

t



(

opti

ona

l)

E

l

e

c

tr

i

c

a

l

he

ater

boa

r

d

(

o

pt

i

o

na

l

)

Ex

tr

a I/

O

b

oar

d

(

opti

onal

)

V

i

br

at

ion tr

ans

mitt

er



boar

d

(

opti

ona

l)

Sp

eed t

r

a

n

sm

itte

r

b

oar

d

(

opti

onal

)

S

t

eam

hea

ter

boar

d

(

o

pt

i

o

na

l

)

Te rm i n a l s

T

r

ans

f

o

r

m

er

P

L

C s

t

anda

r

d

ki

t

4 EPS006

EPC 60 SERVICE ENGINEER TRAINING 2 CONTROL CABINETS

ig 2.2 inside a EPC 60 cabinet with starters

2.2.1 Cabinet with starters

This is a picture of the inside of a cabinet with

starters. Most of what we find inside is familiar

parts but some are new. We have a new AC/DC

converter, new terminals and new contactors

with built in overcurrent protection. We will

explain about the new parts in this chapter.

Emergency stop button:

At delivery, the emergency stop button will be

placed loose inside the control cabinet.

Note that an emergency stop button must

always be installed/connected and within

visible range of the separator.

N

O

T

E

Only in small cabinets without contactors

24VAC to 24VAC transformer;

This is an isolation transformer, needed to

isolate the 24VAC used in the cabinet from the

supplied 24VAC.

This because of legal requirements and to

minimize earth potential related problems.

F

EPS006 5

2 CONTROL CABINETS EPC 60 SERVICE ENGINEER TRAINING

ig 2.3 Contactor w/ over current protection

ig 2.4 With the over current protection removed

2.2.2 Contactor

We have a new supplier for the contactor,

Telemecanique and new design.

The big advantage with the new design is that

the over current protection is built into the

contactor and is detachable. This means if there

has been an error during mounting, you don’t

have to remove the whole part anymore you just

remove the over current protection and mount

the right one in its place. You still have to set

the over current protection correctly as before.

F

Changing the over current protection.

To remove the over current protection you first

have to make sure that the power in the cabinet

is off. Then you have to lift the safety handle on

the unit to unlock it. Grab the handle and pull

the unit out horizontally, take care not to

damage the unit. When fitting the protection

unit on the contactor make sure it is well

pushed into place before locking the safety

handle.

When you change the setting on the protection

unit, you first lift the safety handle and then

the plastic protection lid. Set the correct amp

and then fit the lid and handle.

Make sure the safety handle is fitted correctly

to make sure the protection unit is not vibrating

and coming lose from the contactor; which can

be a fire hazard.

F

6 EPS006

EPC 60 SERVICE ENGINEER TRAINING 2 CONTROL CABINETS

g 2.5 AC/DC converter

erminals w/ level connectors

2.2.3 AC/DC converter

This device converts the 24VAC supplied by the

transformer to 24VDC.

Note that this component has a fuse( 5A)

mounted, protecting the 24VDC output.

The 24VDC is used to supply the EPC60 and all

the analogue sensors and digital inputs.

Note that solenoid valves and contactors are

supplied with 24VAC.

Fi

Terminals:

3 level clamp connection terminals are used.

Note that on some terminals an orange “level

connector” is installed, this is used to connect

the different levels to the same potential.

There are also yellow horizontal connectors

used to connect the same potential to more than

one terminal.

This is snap on terminals, fit a screw driver in

the rectangular hole and push. Fit the cable and

remove the screw driver again.

Pic 2.6 T

EPS006 7

2 CONTROL CABINETS EPC 60 SERVICE ENGINEER TRAINING

Pic 2.7 Innside a small cabinet without contactors.

8 EPS006

EPC 60 SERVICE ENGINEER TRAINING 2 CONTROL CABINETS

2.3 Heater cabinet

There is a new heater cabinet to the new EPC

60. It looks almost the same as the old type, but

some parts are new and there are some changes

in the electrical connections.

The heater cabinet is optional and will only be

delivered when electrical heater controlled by

EPC 60 is ordered.

The size of the cabinet will vary with the size of

the heater. Today we have heaters from 7 to

130kW and 380 to 690V. All systems below 380V

are treated as off spec system and can be ordered

specially.

The new flex system allows easy upgrading to el

heater due to the modular system.

Fig 2.7 Double module w/ heater cabinets

EPS006 9

2 CONTROL CABINETS EPC 60 SERVICE ENGINEER TRAINING

F14

K14K12 K13K11

F13

KA1

1-14

2.3.1 Inside the cabinet

F11 to F14;

Overcurrent protection fuses

K11 to K14;

Contactors

V1 and V2;

Triac solide state relay

S2;

Termo switch

KA11 and KA12;

Interface relays

S1;

Main switch

X;

Terminals

Fig 2.9 Parts in the heater cabinet

V1 V2

X

F12F11

S1

S2

10 EPS006

EPC 60 SERVICE ENGINEER TRAINING 2 CONTROL CABINETS

ig 2.10 The new Triac

Electric heater conections,

From the EPC60 there are 5 signals to the

electric heater cabinet.1 output for variable load,

activating the 2 triacs, 3 outputs to the fixed load

steps. The number used depends on heater size.

There is 1 output for “heater on”, this activates

the K11 inside the electric heater cabinet.

There is also one signal going back to the EPC60,

and this is “Heater fault”.

This signal is expected to be high (active) when

the “heater on” signal is high (active), if not, the

“heater fault” alarm will be activated.

This is normally caused by the over temperature

device, “S2”.

Triacs,

A new type of triac is used, and it is equipped

with a led-indicator, which illuminates when

the triac is active.

The function of the triac itself is the same as the

old type of triacs.

F

EPS006 11

2 CONTROL CABINETS EPC 60 SERVICE ENGINEER TRAINING

12 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

0

8

4 C

0

8

4 C

(2)(3)

odule

nel

l input

t

t

t

input

input

t (optional)

(optional)

tput (optional)

(optional)

t (optional)

2 x Digital input (optional)

RJ 45 exter

nal



c

onne

ctor

o

n

th

e

doo

r

(female

)

input (optional)

3 CPU and I/O

3.1 Inside the cabinets

24VDC

(IN)

24VDC

(IN)

24VDC

401

400

1

6

5

9

1

6

5

9

401

400

(1)

Txd

Rxd

GND

1

2

3

123

Note:

(1) Bridge

(2) Node switch = 0

(3) Node switch = 6

Bus supply m

24 V DC

Operator pa

CPU

6 x Digita

2 x Relay outpu

6 x Relay outpu

4 x Relay outpu

4 x Analogue

2 x Analogue

2 x Relay outpu

1 x Namur input

6 x Relay ou

6 x Digital input

6 x Digital outpu

RJ 45



Plug-in

conn

ector (ma

l

e)

Dsub plug



(ma

le)

C

o

nnect

o

r ca

b

l

e



(f

emale)

2 x Analouge

EPS006 13

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

? A3; 6 digital input

X20 DI 6371

Input from the digital inputs

? A4; 2 relay output

X20 DO 2649

Output ot separator and pump contactor

? A5; 6 relay output

X20 DO 6529

signal to sludge pump, common alarm, SV1,

SV4, cooling fan and steam shut off valve.

? A6; 4 relay output

X20 DO 4529

SV5, SV10, SV15 and SV16

? A7; 4 analogue input

X20 AI 4622

PT5, MT, PT1 and PT4

? A8; 2 analouge input

X20 AT 2222

TT1 and TT2

? A9; 2 relay output (optional)

X20 DO 2649

Steam regulating valve decrease and

increase

? A10; 4 input namur

X20 DI 4760

speed transmitter

? A11; 1 analogue input (optional)

X20 AI 2632

Vibration sensor

? A12; 6 relay output (optional)

X20 DO 6529

Programmable outputs

? A13; 6 Digital input (optional)

X20 DI 6371

Programmable innput

? A14; 6 Digital output (optional)

X20 DO 6322

Electrical heater board

? A15; 2 Digital input (optional)

X20 DI 2371

Heater fault signal.

14 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

A3

501400 401

(1)

X

0

24

68

0

A

Separator em

erg

e

nc

y s

t

o

p

Fee

dback pu

mp

con

ta

ctor

(optio

nal

)

Le

ve

l switch

sludge tank (opti

onal

)

Separator cover



limit swi

t

c

h



(o

ption

a

l)

Slu

d

g

e

valve

interlo

c

k

(o

ption

a

l)

Separator interlock switch Aux. r

e

lay

(optio

nal)

F

eedba

ck

separator



c

ontactor

3.1.1 I/O A3; digital input.

500

N.C.

N.O.

b

Ref. 580879 Sheet 4, Rev. 2

Note:

1. Remove jumper

when used.

EPS006 15

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

A4

501

(1)

(1)

a

X

0

24

68

1

A

C

o

nt

ac

t

o

r

separator

C

o

nt

ac

to

r



feed pump(opti

onal

)

Separator contr

o

l

em

er

ge

nc

y

op

e

r

at

i

o

n

Feed pump contr

o

l emerge

ncy

ope

r

ati

o

n

2

r

e

lay

outpu

t

Co

v

e

r limit

s

witch

(op

t

io

nal)

3.1.2 I/O A4; relay output

500

N.C.

N.O.

N.C.

N.O.

(4)

036

(3)

(2)

Ref. 580879 Sheet 5, Rev. 2

Slu

dge v

a

lv

e

inter

l

oc

k



(op

t

io

nal)

Se

par

ato

r



st

ar

t

e

r o

v

er



32

A

1

)

A

v

ai

lab

l

e

f

o

r emerg

ency

op

er

at

ion

.

2

)

C

o

nnect

i

on when



Co

v

e

r Limit

Swit

ch



is with



on

e co

nta

c

t

.

3

)

C

o

nnect

i

on when



Co

v

e

r Limit

Swit

ch



is not



mo

unt

ed.

4

)

R

e

mo

v

e



ju

m

p

er when used

.

16 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

501

A5

401

X

0

24

68

2

A

Pn

eumatic sludge



pu

mp so

leno

id val

v

e

SV6 (optio

nal)

Co

mmon

a

l

ar

m

Fe

ed sole

noi

d valve



SV

1

PLC co

olin

g fa

n

S

tea

m

shu

t

-of

f



valve

(opti

ona

l)

Oi

l outlet so

len

o

id

valve SV4

6 r

e

lay outpu

t

3.1.3 I/O A5; 6 relay output

400

500

Ref. 580879 Sheet 6, Rev. 2

Shut-of

f

(opti

onal

)

(optiona

l)

EPS006 17

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

A6

501

X

0

24

683

A

Drai

n

va

lve SV5

Displac

ement water



SV

10

Disch

arge val

v

e





SV

1

5

Closi

ng water



SV

16

4 r

e

l

a

y outpu

t

3.1.4 I/O A6; 4 relay output

500

Ref. 580879 Sheet 7, Rev. 2

18 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

A7

401

X

0

24

684

A

W

a

ter outlet p

r

ess

u

r

e



PT

5

W

a

te

r transduce

r



MT

Fe

ed pr

essur

e



PT

1

Oil

o

u

tl

et

p

r

essur

e



PT

4

4 an

a

l

og

ue

in

pu

t

3.1.5 I/O A7; 4 Analogue input

400

Ref. 580879 Sheet 8, Rev. 2

(p

ass

i

v

e

)

(pa

s

siv

e

)

(

pa

ssiv

e)

(a

c

t

iv

e)

EPS006 19

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

A8

X

0

24

68

5

A

T

e

mpe

r

a

t

u

r

e sensor



TT

1

T

e

mperatur

e

se

nsor



TT2

2 Ana

l

ogue input

Se

nso

r

+1

S

ens

or

-

1

S

enso

r

-1

Sen

s

or

+

2

Se

nso

r

-

2

S

enso

r

-

2

3.1.6 I/O A8; 2 Analogue input

Ref. 580879 Sheet 9, Rev. 2

20 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

A9

501

X

0

24

90

4

A

Stea

m r

e

gu

lating valve

co

ntr

o

l

Dec

r

ease

Ste

a

m r

e

gu

lating

valve

co

ntr

o

l

Incr

e

a

se

2 Relay

Outp

ut

3.1.7 I/O A9; 2 relay output

500

M

Ref. 580885 Rev. 2

DecGND

In

c

EPS006 21

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

X

0

24

899

A

4 Input Namur

Sp

ee

d tra

n

smitt

e

r



ST

3.1.8 I/O A10; 4 input namur

Ref. 580887 Rev. 2

22 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

gue input

X

0

24

903

A

3.1.9 I/O A11; 1 analogue input

A11

401

400

Vibration sensor

1 Analo

(active)

From drawing

580879

Ref. 580889 Rev. 2

EPS006 23

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

A14

X

0

24

90

5

A

Electric powerHea

t

e

r

vari

abl

e



load

Electric powerHe

ate

r

step 1

Elect

r

ic power

He

ater step 2

El

ectric po

wer

Heater ste

p

3

Spa

r

e

H

ea

te

r on

6 Digital output

3.1.10 I/O A14; 6 digital output

Ref. 580895 Sheet 1 Rev. 2

24 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

Spare

put

X

0

24

906

A

3.1.11 I/O A15; 2 digital input

A15

Electric heater

Fault feedback signal

2 Digital in

Ref. 580895 Sheet 2 Rev. 2

EPS006 25

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

A12

X

0

24

90

7

A

H

e

a

t

er on

I

n

d

i

cation for

separator

St

and

s

till heating

in

di

cation

Alar

m

High oil te

mperatur

e

Alar

m

Lo

w

o

i

l

temperatur

e

Pr

ogrammable

spa

r

e ou

t

p

u

t

6 Relay ou

tput

3.1.12 I/O A12; 6 relay output

Ref. 580893 Sheet 1 Rev. 1

26 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

A13

400 401

X

0

24

90

8

A

System r

e

mote

star

t

System

r

e

mote

stop

Feed pump

r

e

mote

star

t

Pr

ogrammable

r

e

mote s

p

ar

e

inp

u

t

P

r

og

ra

mm

a

b

le



r

e

mo

te spar

e input

Pr

ogrammable

r

e

mote spar

e input

6 Digital input

3.1.13 I/O A13; 6 digital input

Ref. 580893 Sheet 2 Rev. 1

P

u

lse si

gnal

Pul

s

e



sign

al

Pulse signa

l

EPS006 27

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

ig 3.2 CPU with power supply

ig 3.3 Bus holder for I/O

3.2 CPU

3.2.1 Bus holder

The CPU is the brain in the system. This is the

unit to which all the signals in the system are

sent. All the I/O is connected to the CPU.

There is an Ethernet connection on the CPU

and we use this to communicate with the

Servcom program. We also use Ethernet

connection to download new program versions,

covered in chapter 6.2.

There are two node number switches on the

front of the CPU, called x16 and x1.

The arrow on the x16 should be pointing at 0

while the arrow on the x1 should be pointed at

6.

F

This is the backbone in the I/O system, holding

all the cards together. The holder is common for

all the I/Os and has a snapon function to DIN

rail.

It can be difficult to change one of the holders if

the whole setup is connected to the DIN rail. If

it is necessary to change a holder, remove the

whole setup and change the one damaged and

then connect all holders back on to the DIN rail.

To remove the holder from the DIN rail; lift the

orange handle on top of the holder. To fasten

again, move the orange handle down. Make

sure that all the holders are fastened securely

to the DIN rail; shake the holders to make sure

lock is fastened to the DIN rail.

F

28 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

ig 3.4 Terminal block

3.2.2 Terminal blocks

The terminal blocks are where we connect the

internal cables. This is a standard component

used on all the I/O’s. The connections can vary

from I/O to I/O depending on the function.

To connect a cable; push the black button on top

of the right connection, enter the cable and let

go of the button again.

To remove the terminal block; push down the

handle on top of the block and tilt the top of the

block outwards. There is a guide on the bottom

of the terminal block; make sure the terminal

block is in a horizontal position before removal.

The terminal blocks will not be connected in the

factory due to the possibility of damage to the

I/Os from power surges during ship building.

The conection of the terminals must be done

during commissioning.

F

EPS006 29

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

ig 3.5 I/O DI 6371

3.3 The I/O boards

3.3.1 Change the I/O

The I/O boards gather information and act as

the link between the monitors (i.e. temp and

pressure sensors) and the CPU.

There are ten different I/O boards used for,

digital input, digital output, analogue input and

temperature module.

The picture to the right, Fig 3.3 is an example

on a I/O board . All the different

I/Os are listed in chapter 3.1.

F

To change the I/O board you first have to

remove the terminal block, see info in 3.2.2.

The I/O board is locked to the bus holder and

when removing the I/O push the triangle on top

to unlock. To make sure that the I/O card isn’t

damaged during removal, hold the card in a

horizontal position while removing.

When a new card is fitted this also has to be in a

horizontal position. Make sure that the I/O card

is in final resting position before fitting the

terminal block.

It is important that the right I/O board is fitted

in the correct position. See chapter 3.1 for more

information about the I/O boards. All the boards

have their specific task. Fitting the wrong board

can result in damage to the board(s).

30 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

REMOTE selected on

th REMOTE button in any

ual start, see 1.3 Manual

l switch in a tank.

ion is expected

splay

active

ve

3.4 Programmable Inputs

and Outputs

An extra I/O kit is available as an option. This

kit contains two boards, one with six

programmable digital inputs and one with six

progammable relay outputs. The customer can

select an optional function for each of these

inputs and outputs from a list of alternatives

(see below).

3.4.1 Inputs ( I/O A13)

See parameters 139 to 144.

3.4.2 Outputs (I/O A12)

See parameters P133 to P138.

Alternative Comments

Remote start Enter automatic start, only if

operator panel.

Remote stop Enter stop sequence, works wi

position.

Remote start feed pump The same as first push on man

Start from Standstill, page 9.

External alarm For example, used for a leve

See Alarm 123.

Alternative Comments

Indication heater on/ start

external heater

Activated when heating funct

Indication separator motor on

Indication feed pump on

Standstill indication When ‘Standstill’ shown on di

Indication alarm A20 If alarm ’Oil feed temp. high’

Indication alarm A21 If alarm ’Oil feed temp. low’ acti

EPS006 31

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

ence/Limits

to IB(s)

to IB(s)

lid for:

and P types

nal

lid for:

and P types

lid for:

and P types

lid for:

and P types

lid for:

and P types

3.5 I/O Test Function

This is used during commissioning to test all the

functions and also during fault finding to check

functions on one or more I/O.

Activity Refer

If system has active alarms, check and take actions before

starting the I/O test.

Access the I/O test under settings in the panel, see chapter

4.4.4.

Acc.

Follow the list of I/O‘s (item 25-72) to check status of all el.

connections of the system including the operating function of

individual components.

Acc.

OUTPUTS

K2 - Separator motor

Check the operation and rotation of the separator motor.

The output will only be activated for a short time.

Also check that the correct led is activated on the operating

panel.

Va

All S

If no operation, check jumpers according to electrical

diagram.

K3 – Feed pump

Check the operation and rotation of the feed pump.

Also check that the correct led is activated on the operating

panel.

Optio

Va

All S

If no operation, check jumpers according to electrical

diagram.

V1 – 3 way valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

Va

All S

V4 – Oil outlet valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

Va

All S

Cabinet fan

Verify the operation of the fan mounted inside the electrical

cabinet.

W

A

R

N

IN

G

!

Electrocution Hazard

This operation requires tests to be made with

cabinet door open and with power on.

Beware of live parts.

Va

All S

32 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

tional

alid for:

and P types

alid for:

and P types

tional

alid for:

/615

alid for:

and P types

alid for:

and P types

alid for:

and P types

tional

alid for:

and P types

tional

alid for:

and P types

ference/Limits

Steam shutoff valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

Op

V

All S

V5 - Drain valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

V

All S

Hold/reset vibration switch

Ensure that the vibration switch is reset when this output is

activated

Op

V

P605

SV10 – Displacement water valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

V

All S

SV15 Discharge valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

V

All S

SV16 – Closing water valve

Verify the operation of the valve, see also that the green

diode on the valve connector is lit.

V

All S

Steam decrease – Closing of steam valve

Verify that the valve is moving towards closing position. Note

that if the valve is already closed, an opening operation (see

below) needs to be done prior to this test.

Op

V

All S

Steam increase – Opening of steam valve

Verify that the valve is moving towards opening position.

Op

V

All S

Programmable output 1

Not to be tested

Programmable output 2

Not to be tested

Programmable output 3

Not to be tested

Programmable output 4

Not to be tested

Programmable output 5

Not to be tested

Programmable output 6

Not to be tested

Electric heater test Optional

Before the electric heater i/o-test, please ensure that the

electric power to the electric heater cabinet is turned

OFF!

The operating voltage for the relays is supplied from control

cabinet.

Activity Re

EPS006 33

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

nal

lid for:

and P types

nal

lid for:

and P types

nal

lid for:

and P types

nal

lid for:

and P types

nal

lid for:

and P types

nal

lid for:

and P types

lid for:

and P types

nal

lid for:

and P types

nal

lid for:

and P types

ence/Limits

Elheatvar – Variable output

Check that the diodes on the 2 triacs inside the electric

heater cabinet are lit.

Optio

Va

All S

Heater on signal

Check that the relay KA11 (diode) and K11 (mechanical

indication) in the electric heater cabinet is activated.

Note, leave this output activated (indicating 1 on display)

when proceeding with the tests of the fixed power steps

below!

Optio

Va

All S

ElheatPS1 – Power step 1

Check that the relay KA12 (diode) and K12 (mechanical

indication) in the electric heater cabinet is activated.

Optio

Va

All S

ElheatPS2 – Power step 2

Check that the relay KA13 (diode) and K13 (mechanical

indication) in the electric heater cabinet is activated.

Optio

Va

All S

ElheatPS3 Power step 3

Check that the relay KA14 (diode) and K14 (mechanical

indication) in the electric heater cabinet is activated.

Optio

Va

All S

INPUTS

Heater fault signal

Check that this input is 1 as long as the output “Heater on” is

activated. If not ok, check settings of over temperature

device

Go back to “Heater on” Item no. 47 and deactivate (0 on

display), then go back to this section and verify that “Heater

fault” is 0.

Optio

Va

All S

Estop – Emergency stop

This input should be 1 when emergency stop button is not

pushed.

Press emergency stop button and check that it goes to 0.

Va

All S

Feedback feedpump –

Not to be tested

Feedback separator - Contactor feedback

Not to be tested

Sludge tank level switch

If not installed, check that the input is 1, if not? check if

jumper is installed according to electrical diagram.

If installed, manually operate the level switch, the input

should be 0 when high level.

Optio

Va

All S

Cover switch on separator frame

Manually operate the cover switch, the input should be 1

when switch (and cover) is closed

Optio

Va

All S

Activity Refer

34 EPS006

EPC 60 SERVICE ENGINEER TRAINING 3 CPU AND I/O

tional

alid for:

and P types

mA Input

alid for:

types

mA Input

alid for:

types

mA Input

alid for:

and P types

mA Input

alid for:

and P types

00 input

alid for:

and P types

00 input

alid for:

and P types

ference/Limits

Sludge valve interlock

Manually operate the sludge valve, the input should be 1

when the valve is closed.

Op

V

All S

Programmable input 1

Not to be tested

Programmable input 2

Not to be tested

Programmable input 3

Not to be tested

Programmable input 4

Not to be tested

Programmable input 5

Not to be tested

Programmable input 6

Not to be tested

ANALOGUE INPUTS

PT5 – Water outlet pressure transmitter

Check that the indication shows approx 0 bar.

Note that if pipes are connected to the system, pressure

might not be 0 bar.

4-20

V

All S

MT – Water transducer, MT60

Check that the indication shows 30 pF ±5.

Note that this value is only correct when sensor is in air (no

media in pipes).

4-20

V

All S

PT1 – Oil inlet pressure transmitter

Check that the indication shows approx 0 bar.

Note that if pipes are connected to the system, pressure

might not be 0 bar.

4-20

V

All S

PT4 – Oil outlet pressure transmitter

Check that the indication shows approx 0 bar.

Note that if pipes are connected to the system, pressure

might not be 0 bar.

4-20

V

All S

TT1 – Oil inlet temperature sensor 1

Check that the indication shows a relevant temperature.

PT1

V

All S

TT2 – Oil inlet temperature sensor 2

Check that the indication shows a relevant temperature.

Note that the temperature should not deviate from TT1 with

more than 2 °C

PT1

V

All S

Activity Re

EPS006 35

3 CPU AND I/O EPC 60 SERVICE ENGINEER TRAINING

ur input

nal

lid for:

and P625/635 types

nal

lid for:

5 types

put

nal

lid for:

and P625/635 types

ence/Limits

Speed sensor

In order to test this input, use the “Separator motor”, K2, sect

1, I/O-test to start the separator (for a few seconds), then go

back to this input and check the value, it shall be higher then

0 rpm.

Nam

Optio

Va

All S

Vibration switch

Check that this input goes to 0 when the switch is in tripped

position

Optio

Va

P605/61

Vibration sensor

Check that the indication shows approx 3.5 mm.

(Sensor should be installed with 3.5 mm from the axel)

4-20mA In

Optio

Va

All S

Activity Refer

36 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

546

123

.0

987

i

L

Fig 4.1 EPC 60 Operator panel

4 Operator Panel

The aim of this lession is to present all the

features of the new operator panel; the user

interface, method for parameter adjustment and

program layout.

The operator panel used for EPC60 is based on a

standard panel.

The panel has a 420 signs backlit display.

Some adjustments have been made to suit the

FlexRange;

- Some buttons have been removed and used for

indicators instead (feed pump, heater and

separator).

- The front Mylar (graphics) is adapted for Alfa

Laval, where our symbols and colours are used.

O

I REMOTE

CONTRO

CIP

CLEANING

IN PLACE

SLUDGE

PUMP

DISCHARGE

FEED

PUMP

SEPARATORHEATER

EPS006 37

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

he separator system. When this

quence is initiated. Stepwise or

rameter settings and installed

When this button is pushed the

quence and the separator shuts down

uence, heater, feed pump and separator

on only. The LED will light up with a

lication is started, feed pump,

.

charge controlled by the program.

mote control when activated.

is pushed the system allows the

ogram. Se CIP chapter in service manual

, pump activated when button

owledge and reset alarms.

4.0.1 Buttons

Start button for the operation of t

button is pushed the start se

automatic start depending on pa

equipment

Stop button for the separator system.

system initiates the stop se

step by step; production seq

motor.

Indication; this for informati

green light when the different app

heater and separator motor

Manual discharge; initiates a dis

Remote control; allows for re

See chapter 5.2.3 for more information.

CIP button; when this button

operator to start the CIP pr

for more information.

Manual operation of the sludge pump

pushed.

Alarm button; used to ackn

I

O

FEED

PUMP

SEPARATORHEATER

DISCHARGE

REMOTE

CONTROL

CIP

CLEANING

IN PLACE

SLUDGE

PUMP

38 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

values in the program and for

he menus.

step up and down in the menus and in

information about parameters and

ameters directly, and to load new

Enter button; used to store new

navigation in the menus.

Return button; used to navigate in t

Up and down buttons; used to

the different lists.

Information button; to access

alarms.

Numeric button; to access par

values into parameters.

i

3

EPS006 39

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

Alarm page

1/4 Alarm A21

Oil feed temperature LOW

2/4 Alarm A120

Start blocking

Sludge tank

Level high

4.1 EPC 60 Menus

We will in this chapter go through the menus,

how to navigate in the menus and the menu

structure.

In the new EPC 60 there is a whole new way of

thinking when it comes to menus. The PLC gives

us more flexibility in navigation which in turn

gives a better overview.

Another major change from the older EPC

systems is the operator interface. The new EPC

is much more userfriendly and it is easy to get a

good overview over the menus and parameters.

Navigation in the menus

There are three main pages; Operaing page,

Setting page and Alarmpage.

The operation page is the default page and will

always be visible during operation. To be able to

navigate through the different pages, use the

return button. If the arrows up and down are

used we navigate up or down the same page. See

chapter 4.1.1 for more info regarding buttons.

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

2. Time settings

3. Operation info

TT1 = 98°C

TT2 = 98°C

VIB = 3,49 +- 0,00mm

Discharge = 43m 52s

Speed = 9300rpm

PT 1 = 1,2 bar

PT 4 = 2,2 bar

PT 5 = 2,1 bar

40 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

ere we can check or change the parameters

here we set the time on internal clock

, pump etc

here to read all the alarms

. type and oil type

e to set the right IP address for the sep

assword handling side

Operation page

___Separation___

Flow = 2.8m3/h

Temp= 98°C

Discharge= 43m 52s

SS = 9300rpm

PT1 = 2.10bar

PT4 = 2.30bar

PT5 = 2.20bar

TT1 = 98°C

TT2 = 97°C

Vib = 3.49 +- 0.00mm

MT = 15% 82pF

4.2 Operation page

4.3 Settings page

In the setting page will we find the following sub

menues:

We will go through the sub menus in the

following pages.

In the operation page can we find info regarding

the operation, temperatures, pressures, rpm

and vibration sensor (if mounted). There are 3

parts to this page with 4 lines of information.

We navigate between the different parts with

the up and down buttons.

1 Parameters H

2 Time settings W

3 Operation info Timers on separator

4 I/O test I/O test page

5 Alarm history W

6 System info Info regarding sep

7 IP settings Wher

8 Password/login P

9 Simulator§ Not used

EPS006 41

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

__SET TIME_______

4.3.1 Parameters

We will look at the parameters and parameter

settings in the chapter 5.

4.3.2 Time setting

We use this parameter to set the time during

commissioning. We set the right date and time;

this is used in the alarm lists. We are using GMT

time to have the same time in all our separators

To be able to set the time you have to be logged

in. To set the time; when you are in the set time

menue start with the year and then push the

enter button to save the new value, if not pushed

the new values are not stored.

If you load the wrong value push the back button

and start over. If you only need to change the

date, use the enter button to go to the next value.

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

2. Time settings

3. Operation info

42 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

al time the power has been switched

total running time

running time

otal time in production

otal time in recirculation

otal time temperature exceeds 55°C

otal number of sludge pump activations

otal number of alarm activations

otal volume of separated oil

U temperaure

all the time counters in the PLC

eset all the parameters in the PLC to

ory settings. See parameter list for factory

.

4.3.3 Operation info

We have the following sub menues under

operation info;

1 Timers, counters

2 Reset op info

3 Reset parameters

When we open the sub menue “Timers,

counters”, we find the following info

1 Timers, counters

1.1 Power time The tot

on.

1.2 Sep time Separator motor

1.3 Feed pump time Pump total

1.4 Production time T

1.5 Recirc time T

1.6 Temp >65°C T

1.7 Sludge pump T

1.8 Alarm T

1.9 SepOilVolume T

1.10 CPU temp Actual CP

2 Reset op info

2.1 Reset operation No

information? Yes

Reset

3 Reset parameters

3.1 Reset parameters

to factory No

settings? Yes

Used to r

fact

settings

EPS006 43

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

fo___

2. Sep time

3. Feedpump time

4Production time.

2. Sep time

3. Feedpump time

4Production time.

Menue flow for the Operation info:

When you are in the operation page push the

return button. In the setting page use the up and

down arrows and manoeuvre down to operation

info. Push the enter button.

In the operation page push the enter button on

the menu you want to enter, in this case timers,

counters.

Here you will find all the counters for the

equipment on the unit, like Sep timer, pump

timer etc. push the enter button on the timer you

want to check.

When you are looking at a timer you can

manoeuvre up and down between the timers

with the up and down arrows.

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

2. Time settings

3. Operation info

__Operation in

2. Reset op info

3. Reset parameters

44 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

__I/O_TEST_______ __I/O_TEST_______

__I/O_TEST_______ __I/O_TEST_______

4.3.4 I/O Test

Manoeuvre into the I/O test sub menu.

To start the test; find the object you want to test

and hold the enter buttons pushed. The test is

active as long as the button is pushed. After the

action is confirmd, release the button.

See chapter 3.6 for more information.

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

3. Operation info

4. I/O test

EPS006 45

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

i

4.3.5 Alarm history

To access the Alarm History List at any time

during the operation process press the ‘Return

button’ repeatedly until the Alarm History List

is reached.

Press the arrow buttons to go up or down in the

list. The list consists of the following:

Alarm history – List of alarms which have been

rectified. The latest alarm shows at the top of the

list.

Manoeuvre the > sign in front of the alarm of

interest and then you can press the ‘Information’

button for help and information.If you now use

the down button you get some more info

regarding this alarm.

Press the ‘Information’ button again to return to

your previous position.

46 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

01/50_ALARM_HISTORY_

01/50_ALARM_HISTORY_ A072

Water pressure

sensor Pt5 error

08.02.21 22:10

-Check connections

and cables

Mode: Standstill

Sensor or cable

damaged

Menu flow for the Alarm history:

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

4. I/O test

5. Alarm History

EPS006 47

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

e

__System Info_______

Curretn subnet mask:

255.255.0.0

New subnet mask:

-----------------------

___IP Settings_______

2. Change IP adress

3. Change subnet mask

4.3.6 System info

In system info you only get info regarding type of

separator, what type of oil you are separating

and current program version.

4.3.7 IP settings

IP settings are used when you have more than

one separator in a system with remote control.

Each separator must have a designated IP

address to be able to communicate with the

remote. Se more info in chapter 5.2.3. Remote

control/ monitoring.

Operation page Setting pag

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

5. Alarm History

6. System info

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

6. System info

7. IP settings

48 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

ling_ __PASWORD ______

Enter new password

__PASWORD ______

Confirm new password

__PASWORD ______

Password changed

4.3.8 Password/ Log in

There are three password levels in the new EPC

60.

Level 0 – No password needed.

Level 1 – Possible to protect with password.

Level 2 – Alfa Laval password protected.



Depending on which level you log in; you get

access to different parameters

Level 0;

you get access to language, temperature,

pressure and flow denomination.

Level 1;

the chief engineer can set this password

preventing others on the ship to access level 1

parameters.

Level 2;

gives access to all parameters. This level is

protected by a standard Alfa Laval password,

must not be given to the customer. This

password overrides the level 1 password.

The standard Alfa Laval password is 1361, but

we have three more passwords availalbe if the

password is compromised, 1362, 1363 and 1364.

To change the level one password; manoeuvre to

the password page and choose change user

password. Enter the new password and then

confirm it. The system will confirm that the

password have been changed.

Operation page Setting page

___Separation___

Flow = 2,8m3/h

Temp = 98°C

Discharge = 43m 52s

___Settings___

1. Parameters

2. Time settings

3. Operation info

___Settings___

7. IP settings

8. Password/LogIn

__Password hand

2. Logout

3. Change user pw

EPS006 49

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

i

4.4 Alarms List

If the system has a fault, the alarm LED blinks.

Press the ‘Alarm’ button once. The alarm shows

on the display.

Press the ‘Alarm’ button again to acknowledge

the alarm.

N

O

T

E

The latest 50 alarms are stored in the Alarm History

List. See below.

Press the arrow buttons to go up or down in the

list.

When a list item is blinking, you can press the

‘Information’ button for help and information.

Press the ‘Information’ button again to return to

your previous position.

You can also acknowledge and/or reset this

alarm.

If after all alarms have been acknowledged

fault(s) remain in the system, the alarm LED

stops blinking and remains on. An ‘A’ appears at

the end of an alarm which has not been rectified.

The alarms disappear automatically when the

fault is rectified.

When all the alarms have been rectified, the

alarm LED goes out.

For safety reasons, certain alarms must not only

be acknowledged, but also rectified before the

system can continue in operation, for example

alarm A122 ‘Butterfly valve in sludge outlet

closed’.

Also for safety reasons, some alarms will set the

system into recirculation or stop. These alarms

must be rectified before the operator can put the

system into operation.

Press the ‘Return’ button to leave the list.

50 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

V1

PT4

A50-A59

SS

A110-A111

YT

A100-A103

ST

A90-A97

LS

A120-A121

A122

GS

MT

A80-A85

V4

PT5

V5

A70-A74

X

0

2

4

96

8A

4.4.1 Alarm denomination

T2T P1T

A05

A30-A32

T1T

A20-A25

V10

V15

V16

A40-A43

A01 A15

A130 - A139

EPS006 51

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

Why? What to do

? Feedback signal from

contactor K3 missing.

Check the contactor

function.

Check input terminal in the

PLC.

? Power to heater

interrupted.

Check the power supply to

the heater.

? High temp. switch

released

Check temp. setpoint in

the control unit.

Check the heater and

clean if necessary.

When the temperature

decreases, the switch is

automatically reset.

? Feedback signal from

contactor missing.

Check the contactor

function. Check input

terminal in the PLC.

4.4.2 Alarms on the EPC 60

Alarm

code

Alarm text Conditions

Feed pump (if P127 = yes)

A01 Pump starter

failure

Delayed by P168.

A05 Heater fault

(electric)

Delayed 2 s.

Heater, electric (if P119 = electric)

A15 Separator starter

failure

Delayed 2s.

52 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

? Steam supply valve

faulty

Investigate cause and

remedy.

? Faulty triac module(s) in

the power unit or faulty

controller in the control

unit. (electric heater).

? Broken wiring or

defective heater

resistance, or faulty

controller in the control

unit.

? Heater clogged Investigate cause and

remedy.

? Steam supply

insufficient

Investigate cause and

remedy.

? Steam trap faulty Investigate cause and

remedy.

? Steam supply valve

faulty

Investigate cause and

remedy.

? Faulty fuses or burned

contactors (electric

heater)

Check and renew broken

fuses.

Reset overcurrent

protection (applicable for

8/7 - 24/22 kW power unit).

Check wiring and

contactor coils.

? Broken wiring or

defective heater

resistance (electric

heater)

Check wiring and heater

resistance of each block

or heater element.

? Short circuit / broken

sensor or cable.

Disconnect cable at

sensor. Measure

resistance between 1-3.

Resistance shall be within

100-142 ohms = 0-110 C/

32-230 F.

Replace sensor if broken.

If no spare sensor

available, set parameter

P146 = TT1 to be able to

run the system.

? Insufficient heating

during start.

Check heater function.

Why? What to do

Temperatur transmitter feed inlet TT1

A20 Oil feed

temperature high

Delayed by P150. Limit in

P183.

A21 Oil feed

temperature low

Delayed by P150. Limit in

P184.

A22 Temperature alarm

sensor error (TT1)

Delayed by P150.

A23 Temperature alarm

sensor disabled

Reminder only, if P146 =

TT1

A24 Temperature

increase too slow

Delayed by P169. Limit in

P184.

Alarm

code

Alarm text Conditions

EPS006 53

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

? Heating on during stop

sequence.

Check heater function.

? Recirculating oil not

cooling.

Reset alarm to continue.

? Short circuit / broken

sensor or cable.

Disconnect cable at

sensor. Measure

resistance between 1-3.

Resistance shall be within

100-142 ohms = 0-110 C/

32-230 F.

Replace sensor if broken.

If no spare sensor

available, set parameter

P146 = TT2 to be able to

run the system.

? Pipe restricted. Check recirculation for

restriction.

? Pump not working Check pump.

? Pressure in feed line too

low

Check feed line and flow

regulation.

Check heater for fouling.

? Sensor or cable

damaged.

Check cable connections.

Replace sensor. If no

spare sensor available, set

parameter P157 = 0.

? Increased throughput Check. Reduce

backpressure.

? Regulating valve too

restricted

Adjust valve

Why? What to do

A25 Temperature not

decreasing

Delayed by P173. Limit in

P184. Stop sequence

continues after alarm

reset. Disabled if P173 =

0.

Temperatur transmitter heater control TT2

A30 Temperature

control sensor

error (TT2)

Delayed by P150.

A31 Temperature

control sensor

disabled

Reminder only, if P146 =

TT2

A32 Difference TT1/

TT2 too large

Delayed by P176. Alarm

limit in P177. Blocked if

A22, A23, A30, or A31

Pressure transmitter feed inlet PT1

A40 Feed pressure

PT1 high

Delayed by P150. Limit in

P157.

A41 Feed pressure

PT1 low

Delayed by P150. Limit in

P158.

A42 Feed pressure

sensor PT1 error

Delayed by P150.

A43 PT1 disabled Reminder only, if P157 =

0.

Pressure transmitter oil outlet PT4

A50 Oil backpressure

PT4 high

Delayed by P150. Alarm

limit in P153.

Alarm

code

Alarm text Conditions

54 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

? Decreased throughput Check feed pump and

adjust flow.

? Regulating valve open

too much

Adjust back pressure

valve

? Change over valve V1 in

recirculation position

Check air pressure,

solenoid valve SV1 and

output from EPC 50.

Bowl opens unintentionally

during operation because:

? Strainer and piping in

the operating water

supply is clogged.

Clean the strainer and

check the whole system

fore limestone deposits.

? Too little or no water in

the operating water

system.

Measure the water flow in

the three hoses from the

water block and compare

with correct values.

? Hoses between the

supply valves and

separator are incorrectly

fitted.

Fit hoses correctly.

? Nozzle in bowl body

clogged

Clean the nozzle.

? Rectangular ring in

discharge slide is

defective.

Renew the rectangular

ring.

? Valve plugs are

defective.

Renew all plugs.

? Supply valves SV15 and

SV 16 are leaking.

Rectify the leak.

? Sensor or cable

damaged.

Check cable connections.

Replace sensor. If no

spare sensor available, set

parameter P153 = 0.

? No decrease in oil

pressure at discharge.

Check function of change-

over valve V1.

? No increase in oil

pressure at calibration.

Check supply of

displacement water

(SV10).

? No increase in oil

pressure at

displacement.

Check supply of

displacement water

(SV10).

Why? What to do

A51 Oil backpressure

PT4 low

Delayed by P150. Alarm

limit in P154.

A52 Oil pressure

sensor PT4 error

Delayed by P150.

A53 PT4 disabled Reminder only, if P153 =

0.

A54 Oil pressure PT4

high at discharge

Delayed by P171. Alarm

limit in P221.

A55 No PT4 pressure

feedback at

conditioning water

calibration

Delayed by P170. Alarm

limit in P221.

A56 No PT4 pressure

feedback at

displacement

Delayed by P172. Alarm

limit in P221.

Alarm

code

Alarm text Conditions

EPS006 55

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

? Bowl periphery sealing

damaged

Change seal ring in bowl

hood. Check/change

rubber rings and valve

plugs.

? Leakage somewhere in

oil outlet

Check for leakage.

? Closing water leaking Check/change sealings

and plugs.

? Paring tube not moving

correctly.

Check that movement is

not impeded by friction.

? Paring tube not moving

correctly.

Check that movement is

not impeded by friction.

? Sensor or cable

damaged.

Check cable connections.

Replace sensor. If no

spare sensor available, set

parameter P155 = 0.

? V5 not opening or line

restricted.

Check V5 function.

Clean the outlet pipe.

? Extremely high water

content.

Check where the water is

comimg from.

? Fouling in the MT50. Dismantle and clean with

detergent.

? Too much air in oil

outlet.

Check oil backpressure.

? MT50 test failure. Check water supply.

Check SV10.

? Too much water in oil

outlet.

Investigate cause and

remedy.

? Much water in the feed. Check where the water is

comimg from.

? Paring tube not moving

properly.

Check that movement is

not impeded by friction.

? Sensor or cable

damaged.

Check cable connections.

Replace sensor. If no

spare sensor available, set

parameter P128 = standby.

Why? What to do

A57 Oil leaking from

bowl

Delayed by P245. Alarm

limit in P163.

A58 Leak test failure Limit in P164. No. of

attempts in P166.

A59 PT4 pressure high

during Transition

Delayed by P175. Alarm

limit in P154.

Pressure transmitter water drain PT5

A70 Pressure in water

outlet PT5 high

Delayed by P150. Limit in

P155.

A71 Pressure in water

outlet PT5 low

Delayed by P150. Limit in

P156.

A72 Water pressure

sensor PT5 error

Delayed by P150.

A73 PT5 disabled Reminder only, if P155 =

0.

A74 Water outlet

restricted

Delayed 3s.

Water transducer MT60 (if P117 = yes)

A80 Transducer value

high

Delayed by P150. Limit in

P189.

A81 Transducer value

low

Delayed by P150. Limit in

P162.

A82 MT60 in standby

more than 24

hours

Reminder only, if P128 =

standby more than 24h.

A83 Transducer no

response

Limit in P226.

A84 High water content Number of drainings in

P187. Limit in P224.

A85 MT60 fault Delayed by P150.

Alarm

code

Alarm text Conditions

56 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

? High power (net)

frequency.

Check power supply

before restart.

? Incorrect transmission

parts (50 Hz belt pulley

and belt for 60 Hz power

supply).

W

A

R

N

IN

G

!

Disintegration

hazard

Stop and change the

belt transmission to

suit the power supply

frequency.

? Slipping belt Change belt.

? Worn coupling pads Check / change pads.

? Bowl not properly

closed

Check closing water

supply (valve SV 16).

Check bowl operating

system for leakage.

Check nozzle.

? Bowl not properly

assembled

Check that the lock ring is

in place.

? Low power net

frequency

Check power.

? Motor failure. Repair the motor.

? Bearing(s) damaged. Renew all bearings.

? Incorrect transmission

parts (60 Hz belt pulley

and belt for 50 Hz power

supply).

W

A

R

N

IN

G

!

Disintegration

hazard

Stop and change the

belt transmission to

suit the power supply

frequency.

? Sensor or cable

damaged.

Replace sensor. If no

spare sensor available, set

parameter P179 = 0 to be

able to run the system.

? Power still on to the

motor

Check reason and remedy.

Why? What to do

Speed sensor separator (if P113 = yes)

A90 Bowl speed high Delayed 5 s. Limit in

P179.

A91 Bowl speed low Delayed 5 s. Limit in

P180.

A92 Bowl speed sensor

error

Delay 4s. Timer stop.

A93 Speed sensor

disabled

Reminder only, if P148 =

yes.

A94 Bowl speed high

during STOP

Delayed by P174. Alarm

limit in P180.

Alarm

code

Alarm text Conditions

EPS006 57

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

? Separator friction blocks

slipping

Check the friction blocks.

? Belt slipping Check the belt.

? Height position of paring

disc is incorrect.

Stop. Check and adjust the

height.

? Motor failure Repair the motor.

? Bearing(s) damaged or

worn in coupling or

spindle drive.

Renew all bearings.

? Strainer in the operating

water supply is clogged.

Clean the strainer.

? Water flow too low. Check opening water flow

(SV 15) into the bowl.

? Hoses between the

supply valves and

separator are incorrectly

fitted.

Fit hoses correctly.

? Rectangular ring in the

operating slide is

defective.

Replace the rectangular

ring.

? Sludge remaining in

part of the bowl.

Dismantle, clean and

check the bowl before

restart.

W

A

R

N

IN

G

!

Disintegration

hazard

The separator bowl

must be manually

cleaned before

starting up again.

? Bowl wrongly mounted. Check assembly.

? Disc stack compression

incorrect.

Check assembly.

? Bowl assembled with

parts from other

separators.

Check assembly.

? Height position of paring

disc is incorrect

Stop the separator,

measure and if necessary

adjust the height.

? Bowl spindle bent. Renew the bowl spindle.

Why? What to do

A95 Separator motor

run-up time too

long

Delayed by P230. Limit in

P180.

A96 Slow start

acceleration

Speed < 90 rpm 10s after

response from motor

contactor.

A97 Discharge

feedback error

Alarm limit in P161. Test

during P232, one extra

discharge before alarm.

Vibration sensor separator (if P114 = yes)

A100 High vibration

warning

Delayed by P150. Alarm

limit in P182.

Alarm

code

Alarm text Conditions

58 EPS006

EPC 60 SERVICE ENGINEER TRAINING 4 OPERATOR PANEL

? Bearing(s) damaged or

worn.

Renew all bearings.

? The frame feet are worn

out.

Renew the frame feet.

? Spindle top bearing

spring broken.

Renew all springs.

? Sludge remaining in

part of the bowl

Dismantle, clean and

check the bowl before

restart. See Service

Manual.

W

A

R

N

IN

G

!

Disintegration

hazard

The separator bowl

must be manually

cleaned before

starting up again.

? Bowl wrongly mounted Check assembly.

? Disc stack compression

incorrect

Check assembly.

? Bowl assembled with

parts from other

separators

Check assembly.

? Height position of paring

disc is incorrect.

Stop the separator,

measure and if necessary

adjust the height.

? Bowl spindle bent. Renew the bowl spindle.

? Bearing(s) damaged or

worn.

Renew all bearings.

? The frame feet are worn

out.

Renew the frame feet.

? Spindle top bearing

spring broken.

Renew all springs.

? Sensor or cable

damaged.

Replace sensor. If no

spare sensor available, set

parameter P132 = yes to

be able to run the system.

Why? What to do

A101 High vibration

shutdown

Delay 1s. Alarm limit in

P181.

W

A

R

N

IN

G

!

Disintegration

hazard

If excessive

vibration occurs,

stop separator and

keep bowl filled

with liquid during

rundown.

The cause of the

vibration must be

identified and

corrected before

the separator is

restarted.

A102 Vibration sensor

error

Delayed by P150.

A103 Vibration sensor

disabled

Reminder only. If P132 =

yes.

Alarm

code

Alarm text Conditions

EPS006 59

4 OPERATOR PANEL EPC 60 SERVICE ENGINEER TRAINING

? Separator not properly

assembled

Assemble the separator

according to instructions.

? Faulty frame cover

switch

Replace cover switch. If no

spare switch available, set

parameter P116 = yes to

be able to run the system.

? Pump has not drained

the tank

Check the pump function.

? Valve closed. Open manual valve.

?

? Emergency stop button

pushed

Check for the cause.

Reset pushbutton.

? Too much sludge in

bowl

This alarm is given if the

bowl is extremely dirty and

cannot be acknowledged.

The separator will be

stopped. Wait until STAND

STILL is indicated.

Investigate cause and

remedy.

? Black-out has occurred

during operation.

Check plant conditions

and restart.

? Time in

RECIRCULATION

expired.

Contactor activated 5 times

within last 60 minutes.

Why? What to do

Frame cover switch separator (if P115 = yes)

A110 Frame cover open Delay 1s.

Start not possible.

A111 Cover switch

disabled

Reminder only, if P116 =

yes.

Sludge handling

A120 Sludge tank level

high

At high level: Start not

possible. Sludge pump

running until level signal

normal + 10s. Alarm delay

and max pump running

time 60s in all modes

without feed flow, P159 in

Separation. Discharge

blocked.

A121 Level switch

disabled

Reminder only, if P149 =

yes.

A122 Valve in sludge

outlet closed

Discharge not possible.

Start not possible.

A123 External alarm. Delay 2 s

System

A130 Emergency stop

button pushed

Delay 1s. No restart.

A131 Sludge in bowl Alarm limit in P160.

A132 Power failure Disabled with P152 = no.

A133 Too long time in

RECIRCULATION

Delayed by P178. System

goes to STOP.

A136 Communication

error

A137 Cabinet over

temperature

Reminder only

A138 Too many start

attempts

Alarm

code

Alarm text Conditions

60 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

i

5 Parameters

5.1 Setting List

Parameters are divided into three password

levels:

Level 0 – No password needed.

Level 1 – Possible to protect with password.

Level 2 – Alfa Laval password protected.

To access the Setting List at any time during the

operation process press the ‘Return button’

repeatedly until the Setting List is reached.

When in the setting list; activate the parameter

list. Parameter is flashing. Push the enter button

to enter into the parameter list.

The parameter list is password protected. To be

able to access all the parameters, log in on level 2

with the Alfa Laval password. If not logged

inonly the setting parameters are accessible, i.e.

parameters P100 to P103.

When in the Parameter Menu a list item is

blinking, you can press the ‘Information’ button

for help and information.

Press the ‘Information’ button again to return to

your previous position.

When a list item is blinking, it’s value can be

changed. Push the enter button to activate the

parameter. Changes can be made either by using

the number buttons to write in a value, or by

choosing a value from the list. Save any change

by pressing the ‘Enter’ button.

To leave the changed parameter, push the return

button and go to next parameter.

N

O

T

E

Certain parameters can only be changed by the

factory, the chief engineer, or an Alfa Laval service

engineer.

EPS006 61

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

Additional information

ated!

Flex system (old SA)/ Flex module(old SU)

This parameter is used to determine which oil-

block that is used.

Because Flex system and module have different

oil-block, there is a difference in the flow-

calculation and in order to get as accurate value

as possible, be sure to set this parameter correct

according to the system configuration.

.If this parameter is changed some other

parameter will change, see tabel in the end.

If changed some other parameter will change see

tabel in the end.

It is possible to run the system without vibration

sensor (P114 = no).

In this case alarms A100 – A103 are not

supervised.

Remote start is not allowed.

This also applies if the vibration sensor is disabled

(P132 = yes) or on alarm ‘A102, Vibration sensor

error’.

It is possible to run the system without cover

switch (P115 = no).

In this case alarms A110 – A111 are not

supervised.

Remote start is not allowed.

This also applies if the cover switch is disabled

(P116 = yes).

This parameter is used to soft uninstall the sensor.

When using this parameter a reminder will be

posted in the alarm list until the parameter is set

to NO again. See also P115.

Parameter Denomination

P100 0 Display language: English/German/

Spanish/French/Italian/Portuguese/

Finnish/ Swedish

P101 0 Selection of temp. presentation Celsius/

Fahrenheit

P102 0 Selection of feed flow rate presentation

m

3

/h or USG/h

P103 0 Selection of pressure presentation kPa,

bar, psi

User password required for all following parameters if activ

System configuration

P110 1 Flex configuration

P111 1 Separator size

P112 1 Oil type

P114 1 Vibration sensor installed yes/no

P115 1 Frame cover switch installed yes/no

P116 1 Frame cover switch disabled yes/no

(if P115 = yes)

62 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

It is possible to run the system without water

transducer (P117 = no).

In this case alarms A80 – A85 and A74 are not

supervised.

There is no calibration of the water flow. In

separation, automatic discharges are initiated

every 15 minutes (overrides P220). SV10 is never

activated (this means no displacement before

discharge and no conditioning water). Water

draining from the bowl is not allowed

This also applies if the water transducer is

disabled (P128 = standby) or on alarm ‘A85,

MT60 fault’.

See also "Control of Heater" in the Operating

instructions manual.

Size of the electric heater in the system

The time it take the valve form fully open to fully

closed.

This is the temp difference between the set point

and actual temperature before the system starts

regulating on the heater. Only applicable for

steam heater.

Decreasing the value of this parameter

(proportional band width) will result in a slower

and more stable control action.

See chapter 5.2.1 for more info

Increasing the value of this parameter (integral

time) results in slower response from the EPC-60

See chapter 5.2.1 for more info

The temperature up to which gain facor is active.

Above this temperature normal gain (P-band) is

active.

This factor is used to dcrease the normal P-band

when temperature is below the temperature

defined in P 125. Meaning that when the oil

temperature is low the response from the heater is

quicker.

Standby = MT60 disabled. Discharge every 15

min. (overrides P220). SV10 not activated. No

drain sequence.

When remote control is installed, this parameter

defines the communication method. See chapter

5.2.3 for more information.

Additional information

P117 1 MT60 (water transducer) installed yes/no

P118 1 Sludge pump installed yes/no

P119 1 Heater installed no/electric/steam/

external

P120 1 If P119 = electric: heater size

P121 1 If P119 = steam: steam valve transition

time

P122 1 Deadband heater

P123 1 P-constant heater (if heater controlled)

see also P125/P126 (cold start)

P124 1 I-constant heater (if heater controlled)

P125 1 Breakpoint cold start (if heater controlled)

P126 1 Gain factor cold start (if heater

controlled)

P127 1 Feed pump controlled yes/no

P128 1 MT60 on/standby.

P129 1 Selection of remote control method

digital inputs

Modbus

Parameter Denomination

EPS006 63

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

When stepwise is active the program askes for

confirmation before starting next sequence.

When automatic is active the program start all the

sequences without asking for cinfirmation.

Automatic require some additional installment like

interlock switch, heater conrtol and pump control.

If valve with interloc switch is installed the EPC

monitores the signal and block start if not open.

This parameter is used to soft uninstall the sensor.

When using this parameter a reminder will be

posted in the alarm list until the parameter is set

to NO again. See also P114.

See also “Programmable in- and outputs” in

chapter 5.2.4

see also “Cross connection/serial operation”

in chapter 5.2.5

If the one temp sensor is broken, first try to

replace it and if not possible we can chose to read

the other sensor, remaider is given in the

alarmlist.

It is possible to run the system if the speed sensor

is damaged or broken, set this parameter to YES.

In this case system control and supervision are

much more basic.

Alarms A90 – A97 are not supervised.

Remote start is not allowed.

The start and stop of the separator will be

controlled by time, not sensors.

Additional information

P130 1 Selection of automatic or stepwise start

automatic, stepwise

P131 1 Valve in sludge outlet installed

no, yes

P132 1 Vibration sensor disabled yes/no

P133 1 Optional output 1 (Relay)

P134 1 Optional output 2 (Relay)

P135 1 Optional output 3 (Relay)

P136 1 Optional output 4 (Relay)

P137 1 Optional output 5 (Relay)

P138 1 Optional output 6 (Relay)

P139 1 Optional input 1

P140 1 Optional input 2

P141 1 Optional input 3

P142 1 Optional input 4

P143 1 Optional input 5

P144 1 Optional input 6

P145 1 Cross connection/serial operation

P146 1 Temperature sensor disabled

no, TT1, TT2

P148 1 Speed sensor disabled

P149 1 Level switch disabled. Run sludge pump

30 s at discharge (overrides P234).

Parameter Denomination

64 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

It is possible to run the system with PT4 disabled

(P153 = 0).

In this case alarms A50 – A52 and A54 – A59 are

not supervised.

As a result, calibration of the water flow is not

possible. The old values are used for

displacement and conditioning water. Cold start

function is disabled. Bowl leakage test is disabled.

This also applies on alarm ‘A52, Oil pressure

sensor PT4 error’.

Remeber to set the operational pressure. See

chapter 5.2.2 for more info

It is possible to run the system with PT5 disabled

(P155 = 0).

In this case alarms A70 – A72 and A74 are not

supervised.

This also applies on alarm ‘A72, Water pressure

sensor PT5 error’.

0.0

It is possible to run the system with PT1 disabled

(P157 = 0).

In this case alarms A40 – A42 and A44 are not

supervised.

This also applies on alarm ‘A42, Feed pressure

sensor PT1 error’.

This is the limit used to control the sludge level in

the bowl. if during calibration test the filling time

has decresed with P 160 an alarm is given.

If bowl speed not decreacing P 161 during

discarge, the alarm A97 is given

The accepteble maximum pressure decreace

during bowl leaking test (P245)

The pressure in PT4 has to be under this level

during leakage test.

The pressure in PT4 has to be above this level

during leakage test.

Used to supervise the temperature for instance if

the operator is using a heater not controlled by the

EPC.

Used to supervise the temperature for instance if

the operator is using a heater not controlled by the

EPC.

Additional information

Alarm related parameters: delays, limits etc.

P152 1 Power failure alarm used yes/no

P153 1 High oil pressure limit (PT4), 0.0 =

pressure sensor disabled

P154 1 Low oil pressure limit (PT4)

P155 1 High water pressure limit (PT5), 0.0 =

water pressure sensor disabled

P156 1 Low water pressure limit (PT5)

P157 1 Alarm limit high feed pressure (PT1), 0.0

= feed pressure sensor disabled

P158 1 Alarm limit low feed pressure (PT1)

P160 1 Alarm limit “A131 Sludge in bowl”

P161 1 Alarm limit "A97 Discharge feedback

error"

P162 2 Alarm limit "A81 Transducer value low"

P163 2 Alarm limit "A57 Oil leaking from bowl"

P164 2 High oil pressure limit (PT4) during

leakage test

P165 2 Low oil pressure limit (PT4) during

leakage test

P169 1 Alarm delay "A24 Temperature increase

too slow"

P173 1 Alarm delay “A25 Temperature not

decreasing”

0 = no temperature supervision

Parameter Denomination

EPS006 65

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

If there is pressure in PT4 during start of

separation sequence, i.e. cold oil in the outlet

pipes, the V1 valve will open/ close repetatly

several times. If no presure drop is registered the

alarm A59 is given at P175.

The temperature deviation between TT1 and TT2

before the alarm is activated. If alarm, find the

reason and if sensor is broken, go to P146 to

disable the damaged sensor.

This is not the same function as in EPC 50. This is

the maximum time in recirkulation, when elapsed

separator shuts down.

See Alfa Lavals reccomndations regarding

discharge intervals.

The time V5 is open during draining, timer is

interrupted when transducer value is below P224.

The procentage value where V5 stop draning.

How often we are checking the tarnsducer signal

The value that the trigger limit must excide in the

test.

How often the paring tube is flushed.

SV16 is opened for one sec with the P228

interval.

The time the SV15 is open for discherge

0

Used to prolong the pumping of the sludge tank if

nessesary

V5 and SV10 is opened in order flush out oil from

the paring tube and water outlet.

V5 is open in P237 sec between deplacement

water and discharge to clean the paring tube

The MT 60 signal is tested.

After P239 the new transducer value is taken.

How often we test the calibrated time for

displacement water.

0

Additional information

P175 2 Alarm delay “A59 PT4 pressure high

after cold start"

P177 1 Alarm limit "A32 Difference TT1/TT2 too

large"

P178 1 Time limit in RECIRCULATION

Setpoints

P220 1 Discharge interval

P222 1 V5 open time at drain sequence

P224 1 MT60 limit stop draining

P225 2 Test of MT60 signal (every xxx

discharge), 0 = test disabled

P226 2 MT60 low trigger limit at transducer test

P227 1 Flush of drain outlet after displacement

(every xx discharge)

P228 1 SV16 pulse interval in SEPARATION

P231 1 SV15 opening time

P232 1 Draining of operating water

P233 1 Filling time conditioning water (calculated

during calibration)

P234 1 Sludge pump additional/manual running

time

P236 2 Water drain time during STOP

P237 1 Sludge pump running and V5 opening

time before discharge

P238 2 Feed on after discharge and test of water

content in oil outlet

P239 2 Time for stabilization of the transducer

signal

P242 2 Test of calibration value, interval (no. of

discharges)

P256 1 Feed pump stop delay at normal STOP

Parameter Denomination

66 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

, default 0)

S500

S850

S851

S855

S856

S600

S860

S861

S865

S866

S700

S870

S871

S875

S876

S800

S880

S881

S885

S886

min.

value

max.

value

Unit

89 82 82 81 0 100 % of

P179

(max

speed)

0.5 0.5 0.5 0.5 0.0 2.5 mm

0.3 0.3 0.3 0.3 0.0 2.5 mm

48 80 61 72 0 150

s

5.5 5.5 11.0 15.0 l/min

s 15 s 25 s 35 s 60 s 0 120

s

5 s 5 s 15 s 25 s 25 s 0.1 30.0

s

20 25 30 30 0 30 s

4 6 8 10 10 0 15

s

10 10 10 10 0 15 s

Parameters depending on the setting of P111

Separator size (P111

S811

S816

S200

S821

S826

S820

S825

S300

S830

S831

S835

S836

S400

S840

S841

S845

S846

Parameter Password

level

Description

P180 2 Alarm limit bowl

speed low

83 90 90

P181 2 Alarm limit high

vibration

shutdown

0.3 0.3 0.5

P182 1 Alarm limit high

vibration

warning

0.2 0.2 0.3

P240 1

Filling time

displacement

water, initial

value (calcu-

lated during

calibration,

see also

P254)

77 63 108

SV10, constant

flow orifice

0.9 1.6 1.6

P243 1

SV16 open

after dis-

charge

15 s 15 s 15

P244 1

SV15 open for

priming water

during start-up

5 s 5 s

P245 2 V4 closed

during bowl

leakage test

10 10 20

P247 1 V4 closing delay

at bowl leakage

test

2 2

P248 2 Delay of PT4

pressure

reference value

registration at

bowl leakage

test

5 5 5

EPS006 67

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

with P112)

HF180

HF380

HF460

HF600

HF700

LO TP

Trunk

LO CH

Cross

head

min.

value

max.

value

Unit

105 100 100 0 115

°C

(P101)

85 90 85 0 115

°C

(P101)

98 95 90 0 110

°C

(P101)

2 0 20

0.6 0.1 10.0

pF

100 100 0 250

%

85 78 0 320

pF

0.0 1.0

Parameters depending on the setting of P112

N

O

T

E

If P111 = 0 (default value), the operator is automatically

forced to go through a system configuration procedure to

setup the system.

Oil type (selected

Parameter Pass

word

level

Description GO MDO IF30

IF40

IF60

IF100

P183 1 High

temperature limit

40

P184 1 Low temperature

limit

20

P249 1 Temperature

setpoint

30

P187 2 Number of

drainings before

alarm “A84 High

water content”

5

P251 MT60 trigger

factor

(corresponds to

100% increase

of the transducer

signal)

3.0

P252 1 MT60 trigger

limit

100

P189 2 Alarm limit “A80

Transducer value

high"

110

P254 2 Reduction of

P240 if DO

Calculated as

P240 P254

1.0

68 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

P

0000

41A

Constant amplitude

P00

0051

A

5.2 Additional parameter

info

5.2.1 P & I setting P123 and 124

If the temperature varies with regularly

repeated oscillation, setting of the proportional

band and integral time is necessary.



We recommend you to follow these guidelines:

Set P123 = 10 minutes.

Decrease P-band (P124) in steps until the

process reaches the point where it starts to

oscillate with a constant amplitude. Test the

stability after each step by introducing a step-

change of load or set point.

When you have discovered the point where the

process oscillates with a constant amplitude note

the following figures:

Calculation of optimal parameter settings.

The settings above give a good result but may be

adjusted according to individual characteristics

in different loops.

A = The value of P-band (P123).

B = The time for one full period

in seconds.

P-band I-time

P123 = 2.2 × A P124 = 0.8 × B

EPS006 69

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

5.2.2 Calculating Operating Pressure

Calculate the normal back pressure level during

operation as follows:

Calculate the value for low pressure alarm

setting (Pr 11) as follows:

Calculate the value for high pressure alarm

setting (Pr 10) as follows:

Adjust the back pressure to P

normal



Set Pr 11 to give alarm at pressure decreasing

below the P

low press.

value.

Set Pr 10 to give alarm at pressure increasing

above the P

high press.

value.

P

min

+ P

max



= P

normal



2

P

min

+ P

normal



= P

low press.

2

P

normal

+ P

max

= P

high press.

2

70 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

5.2.3 Remote control/ monitoring

As earlier, remote monitoring is possible on all

the marine separators, but remote control only

on the S-type and P625/635 separators.

Remote control also requires the speed sensor,

vibration sensor and cover interlock switch to be

installed.

There are two ways to use the remote control/

monitoring:

1, Modbus TCP

The customer connects to the EPC60 Ethernet

port (directly to the CPU inside the cabinet, not

using the service Ethernet port on the cabinet

door) and configures his computer to read and

write the data to/from the EPC60.

An instruction on how to connect and where to

read/write these data will be available on

Alround.

2, Digital inputs/outputs,

The programmable digital inputs and outputs,

available on the extra I/O-boards can be used for

remote control/monitoring.

Configure these inputs and outputs with the

parameters P133-144 and connect the remote

control buttons accordingly.

EPS006 71

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

5.2.4 Programmable in- and outputs

As an option, two extra I/O-boards can be

delivered with the EPC60.

The boards are to be used as extra signals.

The function of these inputs and outputs can be

configured with parameters (P133-P144).

If for instance the parameter P136 is set “Heater

on”, the number 4 relay output will be active

(closed) when the EPC60 expects a heater before

the separator to be active.

If P140 is set to “Remote start”, this number 2

input will be possible to connect to a remote start

button, which will activate the remote start

function in the EPC60 when pressed.

This flexibility to choose different functions on

these extra inputs and outputs gives us a

possibility to add extra “special” functions very

easy.

It is only for us to add the software function, and

the new function is directly available as an

output/input when the corresponding parameter

is set.

If you have suggestions on any new function, let

us know, and we will add it.

It could for instance be “remote sludge tank level

switch” or “high PT1 pressure alarm output”.

5.2.5 Cross connection/serial

operation

The cross connection is intended used if there is

a multiple module. Id one heater is broken the

heater on the other system can be used

controlled by the first EPC.

Serial operation is used with Purifiers.

72 EPS006

EPC 60 SERVICE ENGINEER TRAINING 5 PARAMETERS

20mA

320pF0pF

igger

3pF

HFO

100%

0%

83pF

5.3 ALCAP

After P239 (stabilizing period) the new

transducer reference value is taken. This value

will reflect the water content in the oil and vary

from oil to oil since the HFO is different in every

delivery.

The value we take here will be considered “0” on

the trigger range. The 100% on the trigger range

is an increase by 3pF if HFO is chosen in P112

and 0, 6 if LO is chosen in P112. This means that

if we measure the oil to 85pF the 100% trigger

range will be 88pF when handling HFO.

This values for HFO and LO is set in P251 and is

automatically changed when you change the

value in P112. It is possible to adjust the

sensitivity on the trigger range by P252.

If the value in P252 is changed to 200% for

instance, the actual trigger value will be 200% of

the P251 value,

HFO; 3pF 200% = 6pF

LO; 0,6pF 200% = 1,2pF

4mA

0pF 70pF8

Trigger

range

Tr

range

0,6pF

Lube oil

100%

0%

70,6pF

EPS006 73

5 PARAMETERS EPC 60 SERVICE ENGINEER TRAINING

5.3.1 Testing the MT60

The new MT60 uses 4 to 20mA signal and can be

tested in the following way:

? Hold the sensor in air and the value should

be between 30 to 50pF on the panel. The mA

should be 5,5-6,5mA.

? Put the transducer in water and the value

will go above 320pF. You will see 320pF on

the panel and the mA will be 19mA (max

value allowed in the I/O cards).

? Normally the value we measure in oil is

varies between 80 and 90pF.

74 EPS006

EPC 60 SERVICE ENGINEER TRAINING 6 COMPUTER CONNECTION

6 Computer connection

6.1 Computer settup

IP-address setup

This is a general description and for more

information or assistance contact your local IT

department.

In order to download a new application program

or to use Servcom you need to setup your

computer for the Ethernet connection that are

used.

The EPC60 CPU (central processing unit) has a

fixed IP-address which by default is set to

192.168.0.1 and the sub-network is set to

255.255.0.0

These addresses can be changed using the

EPC60 operating panel.

To setup your computer for this connection you

need to change the settings of you network

connection to the same range as the EPC60.

Open the properties for your computers

Ethernet connection, select “Internet protocol

(TCP/IP)” and press properties.

If available, choose the tab “Alternate

Configuration” and configure the settings as

shown to the right.

EPS006 75

6 COMPUTER CONNECTION EPC 60 SERVICE ENGINEER TRAINING

If this tab is not available (depending on version

of windows installed) the configuration should

be according to the picture below.

N

O

T

E

If the tab “Alternate Configuration” was used, it

is possible to leave this setting, because the

connection to the office network will use the

general setting.

If not available, you will need to change back to

the old settings when finished with the EPC60

work in order to get a connection with the office

network.

N

O

T

E

The IP-address in your computer can not be the

same as the CPU.

When these settings are finished, you should

have a connection with the EPC60.

However, settings in the firewall installed by

Alfa Laval, can block the communication

betwenn the EPC 60 and the computer.

If you have problems with the connection, check

with you local it-department that traffic are

allowed to the specified ip-address/subnet and

the port 11159.

76 EPS006

EPC 60 SERVICE ENGINEER TRAINING 6 COMPUTER CONNECTION

6.2 Download of

application software

The latest application software will be found on

Alround (as with the EPC50).

After downloading the zip-file, you need to

extract all the files to a folder.

The zip-file is password protected, and the

password is “Alfa Laval”.

For more info regarding handling of zip-files

contact your local IT-department.

In the EPC 60 we have separate program for

each application, S, P and all the others

comming in the future. There are not longer

necessary to move a jumper to download a new

program. It is not possible to download a new

program when the program is running, the

system have to be in standstill.

To download the software to the EPC60, make

sure that you have your computer setup for the

connection (see chapter 6.1) connect the

Ethernet cable, and then double-click on the

“start. bat” file.

A status-window will appear, and you will see

the progress of the download.

When you see “finished” and “success” in this

window, the download is completed and you can

disconnect the Ethernet cable.

EPS006 77

6 COMPUTER CONNECTION EPC 60 SERVICE ENGINEER TRAINING

78 EPS006

EPC 60 SERVICE ENGINEER TRAINING 7 SERVCOM

7 Servcom

The aim of this lesson is to present all the

features of the new ServCom system; the user

interface, method work and all the new features

of the program.

Servcom is the tool we use to communicate with

the EPC. We had a Servcom for the EPC 50 and

we used that as a template for the new EPC 60

Servcom.

We noticed that the old Servcom had some

drawbacks and decided to make a completely

new Servcom rather than build on the old

design.

The new Servcom thas a lot of new features, such

as new report templates, and a lot of new logging

features. We will go through all the new features

and how to use the program optimally.

Our intention is to develop the Servcom program

further and we need feedback from the users on

what’s good and what’s not. If you have any

suggestions please contact us.

EPS006 79

7 SERVCOM EPC 60 SERVICE ENGINEER TRAINING

7.0.1 Process view

7.0.2 Initial settup

This is the default page in the Servcom. Here

you can see the process, pressures,

temperatures, flow, valve positions, heater load

etc.

There is also a window containing active

alarms. If there is an active alarm the alarm

will be visible in the alarm window and the

actual sensor will be marked red.

Open the “Connection and settings” menu, then

choose “Settings” and check that the “Current

IP setting for EPC60” is in accordance with the

IP-address in the EPC60.

Current ip-setting

Set the IP-address of the CPU, can be read from

the EPC60 panel.

Default IP-address for the CPU is: 192.168.0.1

Ping EPC60

Use this tool to test the communication to the

EPC60.

A successful ping means that the IP-settings in

the computer and EPC60 is correct.

However, connection can still be blocked by i.e.

firewall, check firewall settings with local IT-

department.

Firewall must allow traffic through the selected

IP-address and port 11159.

Debug

Use for advanced faultfinding, will not be

further explained.

80 EPS006

EPC 60 SERVICE ENGINEER TRAINING 7 SERVCOM

7.0.3 Connect to EPC60

7.0.4 Parameter view

To be able to connect to the EPC60 you have to

have the Ethernet cable connected to the CPU

in the cabinet and to the computer.

Open the “Connection and setting” menu and

push the “connect to EPC”. Servcom will now

try to connect and upload all the parameters,

alarm lists and all information stored in the

memory.

To access the parameter list open views in the

top menue and push “Parameters” or push the

parameter quick button.

This is the page where we manage the

parameters. When we are using the Servcom we

have access to all the parameters, no matter the

password level.

The list on the right side is values currently in

EPC 60, and the list to the left is the

parameters in your computer.

The reason for this is safety, you have the

possibility to go through the parameters before

downloading new values into the EPC.

There are some parameters that are dynamic; if

these parameters are changed some other

parameters are changed automatically. The

parameters marked with a green colour (P 111

and P112) are dynamic parameters and will

change several parameters if changed. It is

important that these parameters are changed

first.

Some fields in the parameter list is coloured

gray and not accessible. These parameters (like

P 121 “Steam valve transition time”) are

dependent on the installation. When electrical

heater is installed the P121 will be gray but

when steam heater is chosen it will be opened

for changes..

EPS006 81

7 SERVCOM EPC 60 SERVICE ENGINEER TRAINING

Search for a parameter:

7.0.5 Managing parameters

Click the upper "Find"-button to search for a

certain parameter. This will open a "search

ruler" on top of the parameter list across the

columns.

Enter for instance "low pres" into the Find

textbox, press Enter or click the Find button to

the right of the box.

A list of all parameters with both the text "low"

and the text "pres" in its description appears on

the line to the right.

? Make sure you are connected to the EPC 60

and use the arrow pointing left to upload

the parameters stored in the CPU.

? Change the necessary parameters according to

the installation and download them into the

CPU using the arrow pointing right..

82 EPS006

EPC 60 SERVICE ENGINEER TRAINING 7 SERVCOM

Save parameter

It is possible to save parameters in your

computer for later installations. If you have

more than one separator installed with the

same set up you can save the setup from the

first machine and load it into all the others.

? Open Servcom and change the parameters

according to earlier instruction.

? When the parameters are downloaded to

the CPU, push the “Save to file” button on

the right side. The file will now be stored in

the default file “customerdata”. If you want

the files to be stored somewhere else, make

a new file. Save the file with a name so you

remember what it’s for.

? To download the saved files; connect to the

EPC and upload the parameters from the

CPU with the left pointed arrow. Push the

“Read from file” on the left side and mark

the correct file to download. The saved

values will be imported in the left column.

If there are some parameters that need

changed do it in the left column before

downloading it to the CPU.

To download these values into the CPU,

push the arrow pointing right.

EPS006 83

7 SERVCOM EPC 60 SERVICE ENGINEER TRAINING

7.0.6 Reports

In the new Servcom we have more report

templates. The reason for this is to make it

possible to make uniformed reports that in the

end are made into PDF documents. There can

be attached to any other form of reporting such

sd the SMS.

Another advantage is that all the reports

created can be delivered to the customer on a

memory stick, CD or be sent by e-mail.

To access the different reports open “Reports” in

the top menu and open the report you need. We

will now look into the different reports and how

to use them.’

All the reports created in Servcom will also

contain all serial nos, parameter lists and alarm

history. This is an automatic process but is only

available when Servcom is connected to the

EPC 60.

84 EPS006

EPC 60 SERVICE ENGINEER TRAINING 7 SERVCOM

Claim report

Commissioning report

The claim report is used whenever there are

suspicions that the fault found during service is

a claim situation or when the customer

demands it. A claim is filed into the CSS

system.

In the field “information from customer” note

all the information from the customer. Try to

talk to the customer and make them describe

the fault as detailed as possible. All information

will help in the further investigation.

In the next field “Information about the

installation” fill in all possible information

about the installation. Depending on the

problem, go around, look at everything that can

have any effect on the separation process and

explain the problem in detail.

Under “Problem description” write down the

how you as an engineer find the problem. Be as

specific and detailed as you can, the more

information we gather the better for the further

handling of the claim.

If you find a solution to the problem or have

some thoughts to how to solve the problem,

write it down under “Recommended solution.

The commissioning report is off course used

during commissioning .

The advantage of using this is that when you

create the report in PDF all the parameters,

alarms and serials will be included in the

report. Make one report for every separator.

This report Can be used instead of the

Commissioning check list since they are identical.

EPS006 85

7 SERVCOM EPC 60 SERVICE ENGINEER TRAINING

Summary service report

The summary service report is used during a

normal service, as a normal service report.

In the field “job order” you fill in the reason for

the service and what you are suppose to do.

Under “comments on the service” your write

down all the findings during the service, what

you did and recommendations to the customer.

This can be used as a service report to the

customer if SMS isn’t implemented yet.

On top of all the report templates you will find

five buttons; get last header, clear all, open

draft and create final report as PDF file.

When you fill inn the report and push eider

“save report as draft” or “create final report as

PDF file, the Servcom will store the information

regarding customer, service site and who. Next

time you open a report you can push the “get

last holder” and the Servcom fill in the fields

with the last stored information.

The “clear all” is self explaining.

The “open draft” and “save report as draft”

buttons are a new feature in the Servcom. This

means that you can start a report on the service

sight and save it as draft and then open it again

when you are back in the hotel or in the office

and finish the report there.

When the report is finished you use the “create

final report in PDF format” and the report is

ready for printing or to be used as an

attachment in a mail or in SMS.

86 EPS006

EPC 60 SERVICE ENGINEER TRAINING 7 SERVCOM

EPC 60 alarm history

Serial numbers in EPC60

In the alarm history list we can find the last 50

alarms in the EPC. In the alarm list we can

see alarm code, date and time (real time),

alarm description, mode, timer and timer

name.

Just by looking at the alarm list you can get

lots of information regarding the operation

of the separator.

This list will be a part of all reports and can also

be stored separately as a pdf file.

In this report we get information from the EPC

60 about all serial numbers stored in the

memory. The serial numbers will be entered

into the EPC 60 in the factory, but if a serial

number is missing we can correct this and store

it in the EPC.

? When the page is open push the “Read

serial numbers from EPC60”. All the

parameters stored will now be visible. If

some numbers are missing, they are not

stored in the EPC.

? Write in the missing numbers and push

“Copy serial numbers into EPC60”, this

stores the numbers in the EPC. Thise will

be available for the next engineer uploading

the serial number.

There are also a field here where we can enter

the commissioning date. This can be important

during claim investigation and is something we

must enter.

EPS006 87

7 SERVCOM EPC 60 SERVICE ENGINEER TRAINING

7.0.7 Logging

In the new Servcom 60, the logging function is

vastly improved compared to the older version.

We have a lot more possibilities and many new

features.

When you see the logging for the first time it

can look a little confusing and chaotic, but after

using it a while the new features and

possibilities get clearer.

We will go through the logging functions in this

chapter and try to explain how to use them in

the most effective way.

You have to be connected to the EPC 60 to be

able to log. You can look at a stored log file off

line, we will describe this later.

When you will start logging, push the start

logging button or go to the Logging menu and

use the “Start or Continue logging”. The

program will now open the logging page. The

program has some default variables to log but it

is possible to change these variables.

The default variables are pressure,

temperature, valves, bowl speed and heater

function. The total list is much longer and other

variables can be logged if needed. Push the “set

variables to log” button and choose the ones

that you need to log.

88 EPS006

EPC 60 SERVICE ENGINEER TRAINING 7 SERVCOM

Scaling

It is possible to change the scaling on analogue

curves if you want to look closet at the values.

Right click on the text and the “set vertical (y)

scale” will open. To set your own scale, tic the

“plot curve according to your range settings”

and set your preferred scale in the Max X-axis

and Min Y axis. There will appear a new green

curve working in your settings. If you tic off the

“Plot automatically scaled curve” box the blue

line will disappear or else you will see both lines

and the blue will work on default settings. It is

also possible to increase the curve height by

using the “relative curve height” scale, making

the value even more fine tuned.

This function is also available if you are looking

at a saved file.

Magnifier

During logging the time line will compress

according to logged time. If you want to change

the time line, use the magnifier to extend the

timeline to preferred size. To go back to normal

view again push the “Fit to screen” button.

EPS006 89

7 SERVCOM EPC 60 SERVICE ENGINEER TRAINING

Vertical line

There is a vertical line function in the logging

program. Click on the curve at some interesting

point and a vertical red line will appear. This

line will give you the actual values at this time;

the time is shown beside the line, in reed in the

process value boxes. You can set more than one

vertical line and only the latest is reed showing

the actual process values. If you want to remove

a line click on it again and it will disappear or if

you want to remove all lines push the “reset

curves” button.

There is also possible to left click on an alarm

and a vertical line will appear where the alarm

is initiated in the timeline.

90 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

91

2A

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

91

4A

8 Operating instructions

8.1 Before First Startup

The Control Panel must be configured to suit

the system components.Control Panel

To start the Control Panel, switch on the main

power switch on the control cabinet.

General

The Control Panel has three main lists.

? Operation

? Alarms

? Setting

Operation List

To access the Operation List at any time during

the operation process press the ‘Return button’

repeatedly until the Operation List is reached.

The list gives information on the following where

installed:

? Feed Flow

? Time to discharge, min

? Speed (SS), rpm

? Pressure (PT1, PT4, PT5)

? Temperature (TT1, TT2)

? Vibration (VIB)

? Transducer value

Press the arrow buttons to go up or down in the

list.

N

O

T

E

During operation, the ‘Operation’ list is active on the

display. The present stage of operation, for example

‘SEPARATION’, shows on display together with operating

information such as present temperature.

Press the downward ‘Arrow’ button to go down the list.

EPS006 91

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

2

392

0A

For further information regarding alarms, see

the Alarms and Fault Finding booklet.

For further information regarding parameters,

see the Parameter List booklet.

At any time during operation, the operator can

initiate a STOP sequence by pressing the ‘Stop’

button.

92 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

91

1A

8.2 Manual Start from

Standstill

Press the ‘Start’ button. The operator can select

to start the system manually by setting

parameter P130 to ‘stepwise’.

N

O

T

E

First start-up is always manual and not dependant on

P130 setting.

A rotation test must be carried out using the I/O test

function prior to first start-up.

N

O

T

E

First start-up after power off should always be

carried out manually!

N

O

T

E

If a butterfly valve is installed, it must be opened

manually before that the system can start.

C

A

U

T

IO

N

!

If power cable polarity has been reversed, the separator

will rotate in reverse, and vital rotating parts can loosen.

If speed sensor, vibration sensor, and frame cover

switch are installed (P113, P114, and P115 =

yes), the operator can select to start the system

automatically by setting parameter P130 to

‘automatic’.

EPS006 93

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

91

4

A

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

2

391

3A

If the power has been off and/or the separator

bowl cover has been removed a number of

questions which have to be answered before the

system can be started are shown on the display:

‘Has the bowl been dismantled? YES, NO’

Use the ‘arrow’ buttons to move to the

alternative you want.

When the alternative you want is blinking, press

the ‘Enter’ button.

1 If the bowl has been dismantled choose ‘YES’

Manual start only is possible.

If no work has been carried out on the bowl,

choose ‘NO’. ‘Proceed without calibration’

appears on the display. Stepwise/automatic

start is possible (set using parameter P 130).

N

O

T

E

If this is the first start, answer ‘YES’.

‘Assembled according to manual? YES, NO’

2 If the bowl has been dismantled and

assembled according to the instructions in the

Service Manual, choose ‘YES’.

(If ‘NO’ is chosen, the system goes to

‘STANDSTILL’).

94 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

‘Bowl cleaned? YES, NO’

3 If the bowl has been cleaned choose ‘YES’.

‘Proceed with calibration’ appears on the

display. Local manual start only possible.

If the bowl has not been cleaned, choose

‘NO’. ‘Proceed without calibration’ appears on

the display. Stepwise/automatic start is

possible (set using parameter P 130).

EPS006 95

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

023

91

1A

Start

1 The feed pump (if installed) starts.

The LED on the start button flashes, the LED

for the feed pump lights, and text ‘Starting

feed pump’ shows on the display.

The start button LED shines steadily and the

display shows either ‘To start heater, press

start button’, or ‘To start separator, press start

button’.

96 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

023

91

1A

2 Press the start button a second time.

The heater (if installed) starts.

The LED on the start button flashes, the LED

for the heater lights, and text “Starting heater”

shows on the display.

Wait for increasing temperature.

Cold Start Function

If the viscosity of the oil is high (low

temperature), a smooth heater start-up is

preferred. The temperature up to which the

cold-start gain factor P126 is active is set in

parameter P125. Above this temperature the

normal P-constant P123 is used.

If the temperature has not reached the value

in parameters P184 (HFO/LO low temperature

limit) within the time specified in parameter

P169 (alarm delay), alarm ‘A24 Temperature

increase too slow’ will show on the display.

If the temperature feedback is correct

(reading on temperature sensor TT1 above

value in parameter P184), the start button LED

shines steadily and the display shows ‘To start

separator, press start button’.

EPS006 97

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

023

91

1A

3 Press the start button a third time.

The separator motor starts.

The LED on the start button flashes, the LED

for the separator lights, and text ‘Starting

separator’ shows on the display.

Wait for speed feedback (if speed sensor

installed), or until the separator max. start time

(4 minutes) has elapsed.

If the speed has not increased to over 90 rpm

within 10 seconds after contactor K2

response, alarm ‘A96 Slow start acceleration’

shows on the display.

If the low speed limit value in parameter P180

has not been reached before the separator

max. start time has elapsed, alarm ‘A95

Separator motor run-up time too long’ shows

on the display.

If the separator is running above the low

speed limit, the start button LED shines

steadily, and the display shows the heading

‘RECIRCULATION’ and text ‘To start

separation, press start button’.

98 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

023

91

1A

4 Press the start button a fourth time.

If the feed temperature is below the value in

P184, the controller stays in RECIRCULATION

mode. The LED on the start button flashes,

and text ‘Waiting in RECIRCULATION for

separation temperature’ shows on the display.

If the correct feed temperature is reached, the

controller changes automatically to

SEPARATION mode via a transition sequence

which is shown on the display. The start button

LED shines steadily, and the display shows

the heading ‘TRANSITION’.

If speed sensor not installed (P113 = no) or

disabled (P148 = 0), change over to

RECIRCULATION/SEPARATION takes place

when the separator max. start time has

elapsed.

N

O

T

E

The time in ‘RECIRCULATION’ is limited by timer

P178 to avoid overheating of the separator.

EPS006 99

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

8.3 Automatic Start from

Standstill

The operator can select to start the system

automatically by setting parameter P130 to

‘automatic’.

The control panel automatically goes through

the same procedure as described under 1.3

Manual Start from Standstill.

If the bowl has not been dismantled or cleaned,

the previously calculated filling time (parameter

P233) is used, a discharge sequence and a bowl

leakage/water transducer test are run, and the

system goes into SEPARATION mode.

The following equipment must be installed for

automatic start:

? Vibration monitor

? Speed sensor

? Frame cover switch

100 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

FEED

PUMP

HEATER

SEPARATOR

X

0

2

392

3A

8.4 During separation

Observe information on the control panel

display. The times in each sequence are shown in

the bottom left-hand corner of the displa

Discharge sequences run automatically at pre-

set intervals (timer P220).

Discharge sequence can also be run manually by

pressing the ‘Discharge’ button.

EPS006 101

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

2

392

2A

The Sludge Pump runs during discharge or when

there is high level in the sludge tank, or can be

started manually by pressing the ‘Sludge Pump’

button on the control panel.

N

O

T

E

Do not run the sludge pump longer than necessary. If

the pump is run while dry it can be damaged.

In SEPARATION mode, the feed pump is

running, the feed has reached separation

temperature (the heater is working) and the

separator is running at full speed.

Feed valve V1 is open to the separator inlet.

102 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

92

0A

8.5 Stop

C

A

U

T

IO

N

!

Breakdown hazard

Stop the separator by means of the control unit, and

not by turning off the power.

C

A

U

T

IO

N

!

Never attempt to clean the bowl by manual discharge

in connection with stop.

To stop the system

The operator can stop the system when in the

‘START’, RECIRCULATION’, or ‘SEPARATION’

modes.

1 Stop the system by pushing the ‘Stop’ button

on the control panel. The following sequence

takes place:

? A stop discharge and flushing sequence are

initiated (does not apply to stop from ‘START’).

N

O

T

E

Filling and flushing are not performed if the

discharge feedback has not been received.

EPS006 103

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

N

O

T

E

If the system is switched off, it can in most cases

be switched on again without waiting for the

separator to slow down. See 8.2 Manual Start

from Standstill, page 99, and the Alarms and

Fault Finding booklet.

? The separator motor is turned off and the stop-

timer starts running. At the same time, the

heater is turned off (see 8.6.4 Heater shut

down, page 120). The system waits for the

feed temperature and speed to decrease.

? If the speed limit in P180 (low speed limit) is

not reached within 3 minutes, alarm ‘A94 Bowl

speed high during STOP’ is given.

? When the bowl speed has reached 4000 rpm,

closing water valve SV16 is activated for 1

second in order to keep the bowl closed.

? If speed sensor not installed (P113 = no) or

disabled (P148 = 0), SV16 opens for 1 second

5 minutes after the separator motor has been

turned off.

? When 3 minutes has elapsed, the feed pump

is turned off.

? The system waits for the speed sensor (if

installed) to indicate zero speed. When the

bowl has been still for 60 seconds, ‘STAND

STILL’ shows on the display.

? If speed sensor not installed (P113 = no) or

disabled (P148 = 0), ‘STAND STILL’ is shown

when the stop timer has elapsed.

? The sludge pump runs for 10 seconds after

STAND STILL is reached if stopped from

SEPARATION mode or RECIRCULATION

mode.

? All equipment except the sludge pump (which

can still be run manually) is now deactivated.

104 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

92

1A

8.5.1 CIP Start

CIP can be selected from STAND STILL only,

and only from a local control panel.

Press the CIP button to select CIP.

N

O

T

E

During CIP the separator is running at full speed, but feed

pump, heater, process valves, temperature and pressure

supervision and water transducer MT60 are neither

controlled nor supervised.

EPS006 105

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

91

1A

With CIP selected from STAND STILL, press the

‘START’ button to start the separator motor. The

motor starts unless the system prevents start, or

alarms are active.

Wait for speed feedback.

? Speed has to increase to above 90 rpm within

10 seconds after contactor K2 response,

otherwise alarm ‘A96 Slow start acceleration’

will be shown on the display.

? Speed limit in parameter P180 has to be

reached within 4 minutes, otherwise alarm

‘A95 Separator motor run-up time too long’ will

be shown on the display.

? When the separator is running above low

speed limit (P180), or 4 minutes has elapsed if

speed sensor not installed (P113 = no) or

disabled (P148 = 0), a message to start the

cleaning liquid supply is given to the operator.

106 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

92

2A

CIP Running

N

O

T

E

When the bowl has reached normal speed, a bowl

closing procedure will be performed.

While the CIP system is running, closing water

valve SV16 opens for 2 seconds and closes for the

time set in parameter P228 (pulse interval)

repeatedly. The sludge pump runs when there is

high level in the sludge tank or when activated

by pressing the ‘SLUDGE PUMP’ button on the

control panel.

EPS006 107

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

9

6

3

8

2

0

7

4

1

.

i

5

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

FEED

PUMP

HEATER

SEPARATOR

X

0

23

92

3A

A discharge can be activated manually during

the CIP process by pressing the ‘DISCHARGE’

button on the control panel.

108 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

9

6

3

8

2

0

7

4

1

.

i

5

SLUDGE

PUMP

CLEANING

IN PLACE

REMOTE

CONTROL

CIP

DISCHARGE

FEED

PUMP

HEATER

SEPARATOR

X

0

23

92

0

A

CIP Stop

Stop the CIP process by pressing the ‘Stop’

button on the control panel. The CIP process can

be restarted.

? The separator motor is turned off. Alarm delay

(3 minutes) starts, and stop timer starts. If the

speed limit in parameter P180 (alarm limit

bowl speed low) is not reached within 3

minutes, alarm ‘A9 Bowl speed high during

STOP’ is given.

? When the bowl speed has reached 4000 rpm,

closing water valve SV16 is activated for 1

second in order to keep the bowl closed.

? If there is no speed sensor installed

(parameter P113 = no) or disabled (parameter

P148 = 0), SV16 opens for 1 second 5 minutes

after the separator motor has been turned off.

? The system waits for the speed sensor (if

installed) to indicate zero speed. When the

bowl has been still for 60 seconds, ‘STAND

STILL’ shows on the display.

? If there is no speed sensor installed

(parameter P113 = no) or if speed sensor

disabled (parameter P148 = 0), ‘STAND STILL’

is shown when stop timer has elapsed.

? If the bowl speed has been above P180, or

the start timer has elapsed, the sludge pump

runs for 10 seconds after ‘STANDSTILL’.

? Hold the ‘CIP’ button pressed for 5 seconds to

leave CIP mode.

EPS006 109

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

8.6 Heater Control

(optional)

The temperature in the feed inlet is normally

supervised via TT1, and can be controlled by a

heater via TT2. Supervision and control are

active even if one of the sensors is disabled.

The heater is controlled according to

temperature setpoint P249 using a PI-regulator:

Out = ((I + E) 100) / (200 P123) where

Out = output signal to the heater

E = difference between reading on TT2 and P249

I= I+ E/P124

P123 = P-constant

P124 = I-constant. Every second a new output

value is calculated.

With P119 it is possible to select heater control

mode:

no (no heater controlled)

electric (electric heater controlled, P120 active)

steam (steam heater controlled via three

outputs, P121 active)

external (start/stop request via programmable

output, heater not controlled)

If the viscosity of the oil is high (low

temperature), a smooth start-up of the heater

might be favourable. The temperature, up to

which the cold-start gain factor P126 is active, is

set in P125. Above this temperature the normal

P-constant P123 is used.

Example: P123 = 30, P126 = 40 results in gain

below P125 of 0.40 x 30 = 12

110 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

8.6.1 Control of the electric heater

(optional)

P119 = electric.

Six outputs and one input are used to control the

electric heater:

? Four relay outputs to up to four fixed power

steps depending on the heater size (P120)

? one variable load output

? one output "heater on"

? one input "heater fault" (see A05)

The total heater capacity (100%) is the sum of

the power available at the four fixed steps, plus

the power available via the variable load output

(always 16 kW nominal).

This means, if the output signal to the heater is

100%, all available power steps and the variable

load output have to be activated continuously.

Output signal 0% means that all outputs are

deactivated.

If the output signal is a value between 0 and

100%, the activation pattern of the outputs has

to be calculated using the table below.For each

value of P120 the contribution of each power step

to the total available heater capacity is given in

percent. First use the fixed power steps to fill the

power requirement as far as possible, then use

the variable load output to fine adjust the

output.

As a new output signal is calculated every

second, the variable load output is activated for

parts (0.1) of a second.

0.1 s activates 1/10 of the available power on the

output = 1.6 kW.

0.5 s means 8 kW and so on.

EPS006 111

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

ower step 3 Variable load output

%

10 x 10

10 x 10

10 x 6.6

10 x 4

.5 10 x 2.9

10 x 2.2

.5 10 x 2.9

10 x 2.2

Example 1: Heater size 72 kW and output signal

to the heater 50%. Activate step 3 (for 1s) and

activate var. output for 0.2s.

Example 2: Heater size 16 kW and output signal

to the heater 88%. Activate var. output for 0.9s.

Example 3: Heater size 144 kW and output

signal to heater 88%. Activate steps 1, 2, 3 and 4

(for 1s).

To prevent problems with too heavy momentary

load at start of the heater, only one output can be

activated per second during the first 6 seconds.

After that time all outputs can be used

simultaneously.

Output power (in % of the total available power)

Heater size (kW nominal,

selected with P120)

Power step 1

%

Power step 2

%

P

%

7, 8 0 0 0

14, 16 0 0 0

22, 24 33.5 0 0

36, 40 20 40 0

50, 56 14.3 28.5 28

65, 72 11 22 45

100 14.3 28.5 28

130 11 22 45

112 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

8.6.2 Control of the CBM heater

(optional)

P119 = steam. In this case alarm A05 is not

supervised.

The steam heater is controlled using three relay

outputs:

? increment steam valve

? decrement steam valve

? steam shut-off valve (hold signal)

The position of the valve is not supervised.

The transition time of the steam valve is set in

P121 (time from fully open to fully closed

position and vice versa). The controller function

defines if the valve should be opened

(incremented) or closed(decremented) in relation

to its actual position.

The signal to the steam valve is pulsed with an

on-time corresponding to the temperature

controller output. Example: output = +50%

means the increment steam valve output is

activated for 0.50 s/s.

When the heater is stopped, the decrement

steam valve signal is on for the time set in P121.

The hold signal is off if the start of the heater is

interlocked (e.g. on alarms A01, A20).

8.6.3 If heater not controlled or

external

It is possible to run the system without heater

control (P119 = no).

In this case alarms A05, A24 and A25 are not

supervised.

It is also possible to run the system with

external heater (P119 = external). The ‘heater

on’ signal is given via a programmable output.

In this case alarm A05 is not supervised.

The description for the system with external

heater is also valid if one of the temperature

sensors is disabled or on sensor error (A22/A30).

EPS006 113

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

8.6.4 Heater shut down

The system waits for the feed temperature to

decrease (5 degrees or below P184). If the time in

P173 has elapsed and the temperature feedback

was not received, alarm ‘A25 Temperature not

decreasing’ is given.

When the temperature feedback has been

received, or P173 has elapsed, P256 is started.

When P256 has elapsed, the feed pump (if

running) is turned off. If the feedback signal

from the pump contactor is not received within 5

seconds, alarm ‘A01 Pump starter failure’ is

given.

N

O

T

E

Heater shutdown is also initiated at STOP request

during START if feed pump and heater are on but the

separator is not running.

114 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

8.7 Operation without all

sensors

(Emergency operation)

8.7.1 System Without Speed Sensor

It is possible to run the system without speed

sensor (P113 = no).

In this case system control and supervision are

much more basic.

Alarms A90 – A97 are not supervised.

Remote start is not allowed.

The separator is started within 4 minutes and

stopped with stop timer.

This also applies if the speed sensor is disabled

(P148 = 0) or on alarm ‘A92, Bowl speed sensor

error’.

8.7.2 System Without Vibration

Sensor

It is possible to run the system without vibration

sensor (P114 = no).

In this case alarms A100 – A103 are not

supervised.

Remote start is not allowed.

This also applies if the vibration sensor is

disabled (P132 = yes) or on alarm ‘A102,

Vibration sensor error’.

8.7.3 System Without Cover Switch

It is possible to run the system without cover

switch (P115 = no).

In this case alarms A110 – A111 are not

supervised.

Remote start is not allowed.

This also applies if the cover switch is disabled

(P116 = yes).

EPS006 115

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

8.7.4 System With PT1 Disabled

It is possible to run the system with PT1

disabled (P157 = 0).

In this case alarms A40 – A42 and A44 are not

supervised.

This also applies on alarm ‘A42, Feed pressure

sensor PT1 error’.

8.7.5 System With PT4 Disabled

It is possible to run the system with PT4

disabled (P153 = 0).

In this case alarms A50 – A52 and A54 – A59 are

not supervised.

As a result, calibration of the water flow is not

possible. The old values are used for

displacement and conditioning water. Cold start

function is disabled. Bowl leakage test is

disabled.

This also applies on alarm ‘A52, Oil pressure

sensor PT4 error’.

8.7.6 System With PT5 Disabled (S-

separator only)

It is possible to run the system with PT5

disabled (P155 = 0).

In this case alarms A70 – A72 and A74 are not

supervised.

This also applies on alarm ‘A72, Water pressure

sensor PT5 error’.

116 EPS006

EPC 60 SERVICE ENGINEER TRAINING 8 OPERATING INSTRUCTIONS

8.7.7 Control of Sludge Pump, Level

in Sludge Tank, and Butterfly

Valve

The sludge accumulated in the bowl can be

discharged into an optional small sludge tank

with level switch. At high level signal a sludge

pump (P118 = yes) is running until the signal is

normal + 10 seconds . Otherwise see alarm A120.

The level switch can be disabled (P159 = 0). In

this case A120 is blocked and the sludge pump is

running for 30 seconds at discharge (instead of

P234, see below).

The sludge pump is also activated during certain

timers. These running times are always

terminated by an extra pump running time (e.g.

during P234, or 5 seconds as in the drain

sequence). Note that this extra time is

independent of the other timers which may be

running simultaneously.

See also the Sequence diagram for other

occasions when the sludge pump is activated, if

selected (Parameter List chapter ‘2.2 Discharge’)

.

The separator sludge outlet can contain a

manual butterfly valve which is used to close the

outlet when the separator is standing still.

Select with P131 (no, manual).

If P131 = no, alarm A122 is blocked.

EPS006 117

8 OPERATING INSTRUCTIONS EPC 60 SERVICE ENGINEER TRAINING

8.7.8 System Without Feed Pump

It is possible to run the system without feed

pump (P127 = no).

In this case alarms A01 and A44 are not

supervised.

Remote start is not allowed.

8.7.9 System Without Water

Transducer (S-separator only)

It is possible to run the system without water

transducer (P117 = no).

In this case alarms A80 – A85 and A74 are not

supervised.

There is no calibration of the water flow. In

separation, automatic discharges are initiated

every 15 minutes (overrides P220). SV10 is never

activated (this means no displacement before

discharge and no conditioning water). Water

draining from the bowl is not allowed

This also applies if the water transducer is

disabled (P128 = standby) or on alarm ‘A85,

MT60 fault’.

118 EPS006

献花(0)
+1
(本文系wangweiqin1...首藏)