配色: 字号:
空气干燥器
2023-06-17 | 阅:  转:  |  分享 
  
INSTRUCTION BOOK

REFRIGERANT COMPRESSED AIR DRYERS

FX 1, FX 2, FX 3, FX 4, FX 5, FX 6, FX 7



Atlas Copco

Refrigerant compressed air dryers

FX 1, FX 2, FX 3, FX 4, FX 5, FX 6, FX 7

From following serial No. onwards: ITJ 169 435

Instruction book

Original instructions

COPYRIGHT NOTICE

Any unauthorized use or copying of the contents or any part thereof is prohibited.

This applies in particular to trademarks, model denominations, part numbers and

drawings.

This instruction book is valid for CE as well as non-CE labelled machines. It meets the

requirements for instructions specified by the applicable European directives as

identified in the Declaration of Conformity.

2018 - 10

No. 2920 7112 41

www.atlascopco.com

Table of contents

1 Safety precautions..........................................................................................................4

1.1 SAFETY ICONS...................................................................................................................................4

1.2 SAFETY PRECAUTIONS, GENERAL...........................................................................................................4

1.3 SAFETY PRECAUTIONS DURING INSTALLATION...........................................................................................5

1.4 SAFETY PRECAUTIONS DURING OPERATION..............................................................................................6

1.5 SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR...........................................................................7

1.6 DISMANTLING AND DISPOSAL.................................................................................................................8

2 General description......................................................................................................10

2.1 INTRODUCTION.................................................................................................................................10

2.2 AIR SYSTEM....................................................................................................................................12

2.3 REFRIGERATION SYSTEM....................................................................................................................13

2.4 AUTOMATIC REGULATION SYSTEM........................................................................................................13

2.5 ELECTRICAL SYSTEM.........................................................................................................................14

3 Installation.....................................................................................................................15

3.1 DIMENSION DRAWINGS.......................................................................................................................15

3.2 INSTALLATION PROPOSAL...................................................................................................................15

3.3 PICTOGRAPHS.................................................................................................................................18

4 Operating instructions.................................................................................................19

4.1 WARNINGS......................................................................................................................................19

4.2 DRYER CONTROL PANEL ...................................................................................................................19

4.3 DIGITAL DRYER CONTROLLER..............................................................................................................20

4.4 STARTING.......................................................................................................................................26

4.5 DURING OPERATION..........................................................................................................................27

4.6 STOPPING.......................................................................................................................................27

Instruction book

2 2920 7112 41

5 Maintenance instructions............................................................................................ 29

6 Device settings............................................................................................................. 31

7 Problem solving............................................................................................................32

8 Technical data...............................................................................................................35

8.1 REFERENCE CONDITIONS AND LIMITATIONS............................................................................................35

8.2 AIR DRYER DATA..............................................................................................................................36

9 Pressure equipment directives................................................................................... 40

10 Declaration of conformity............................................................................................41

Instruction book

2920 7112 41 3

1 Safety precautions

1.1 Safety icons

Explanation

Danger to life

Warning

Important note

1.2 Safety precautions, general

General precautions

All responsibility for any damage or injury resulting from neglecting these precautions, or

non-observance of the normal caution and care required for installation, operation,

maintenance and repair, even if not expressly stated, will be disclaimed by the

manufacturer.

1. The dryers are designed for normal indoor use.

2. The operator must employ safe working practices and observe all related work safety

requirements and regulations.

3. If any of the following statements does not comply with the applicable legislation, the stricter

of the two shall apply.

4. Installation, operation, maintenance and repair work must only be performed by authorized,

trained, specialized personnel.

5. The dryer is not considered capable of producing air of breathing quality. To obtain air of

breathing quality, the compressed air must be adequately purified according to the

applicable legislation and standards.

6. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the

dryer, press the emergency stop button, switch off the voltage and depressurize the dryer. In

addition, the power isolating switch must be opened and locked. For plug versions, remove

the plug from the wall socket and secure it.

7. Never play with compressed air. Do not apply the air to your skin or direct an air stream at

people. Never use the air to clean dirt from your clothes. When using the air to clean

equipment, do so with extreme caution and wear eye protection.

8. The owner is responsible for maintaining the dryer in safe operating condition. Parts and

accessories shall be replaced if unsuitable for safe operation.

9. It is not allowed to walk or stand on the dryer or its components.

Instruction book

4 2920 7112 41

1.3 Safety precautions during installation

Precautions during installation

1. The dryer must only be lifted using suitable equipment and in accordance with the applicable

safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is

strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and

deceleration must be kept within safe limits. Wear a safety helmet when working in the area

of overhead or lifting equipment.

2. Place the dryer where the ambient air is as cool and clean as possible. If necessary, install a

suction duct. Never obstruct the air inlet. Care must be taken to minimize the entry of

moisture at the inlet air.

3. Any blanking flanges, plugs, caps or desiccant bags must be removed before connecting the

pipes.

4. Air hoses must be of correct size and suitable for the working pressure. Never use frayed,

damaged or worn hoses. Distribution pipes and connections must be of the correct size and

suitable for the working pressure.

5. The aspirated air must be free of flammable fumes, vapours and particles, e.g. paint

solvents, that can lead to internal fire or explosion.

6. Arrange the air intake so that loose clothing worn by people cannot be sucked in.

7. Ensure that all piping is free to expand under heat and that it is not in contact with or close to

flammable materials.

8. No external force may be exerted on the air outlet valve. The connected pipe must be free of

strain.

9. If remote control is installed, the machine must bear a clear sign stating "Danger: This

machine is remotely controlled and may start without warning".

The operator has to make sure that the machine is stopped and that the isolating switch is

open and locked before any maintenance or repair. As a further safeguard, persons

switching on remotely controlled machines shall take adequate precautions to ensure that

there is no one checking or working on the machine. To this end, a suitable notice shall be

affixed to the starting equipment.

10. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is

available and that the exhausted cooling air does not recirculate to the inlet.

11. The electrical connections must correspond to the applicable codes. The machines must be

earthed and protected against short circuits by fuses in all phases. A lockable power

isolating switch must be installed near the equipment.

12. On machines with automatic start-stop system or if the automatic restart function after

voltage failure is activated, a sign stating "This machine may start without warning" must be

affixed near the instrument panel.

13. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.

Every pressure vessel or auxiliary installed outside the machine to contain air above

atmospheric pressure must be protected by a pressure-relieving device or devices as

required.

14. Piping or other parts with a temperature in excess of 80?C (176?F) and which may be

accidentally touched by personnel during normal operation must be guarded or insulated.

Other high-temperature piping must be clearly marked.

15. For water-cooled machines, the cooling water system installed outside the machine has to

be protected by a safety device with set pressure according to the maximum cooling water

inlet pressure.

16. If no safety valve is present in the air net close to the desiccant dryer (e.g. safety valve of

compressor), full flow safety valves must be installed on the dryer vessels.

Instruction book

2920 7112 41 5

17. If the maximum pressure of the compressor is higher than the design pressure of the dryer,

a full flow safety valve must be installed between the compressor and the dryer in order to

blow off the excessive pressure in case the safety valve of the dryer should be out of order

or blocked.

18. When unit is not permanently secured to the floor in the vertical position or mounted

horizontally, access to electrical equipment is feasible through the unit base. In this case

additional barriers must be provided during installation. Tag with "warning high voltage"

symbol

19. For wall fixation and mounting use M8 hexagonal galvanized steel screws according to

UNI5740-DIN961-UNI_EN_ISO8676 or equivalent for extra-EU countries, with a minimum

resistance class of 5,6. This suggestion is valid only to keep on standing the dryer weight.

The manufactures declines any responsibility of improper screw selection or improper

characteristic of the wall where the dryer has to be fixed.

Also consult following safety precautions: Safety precautions during operation and Safety

precautions during maintenance or repair.

These precautions apply to machinery processing or consuming air or inert gas. Processing

of any other gas requires additional safety precautions typical to the application which are

not included herein.

Some precautions are general and cover several machine types and equipment; hence

some statements may not apply to your machine.

1.4 Safety precautions during operation

Precautions during operation

1. Always be careful when touching any piping or components of the dryer during operation.

On dryers using heat to regenerate the desiccant, some parts will become very hot.

2. Use only the correct type and size of hose end fittings and connections. When blowing

through a hose or air line, ensure that the open end is held securely. A free end will whip

and may cause injury. Make sure that a hose is fully depressurized before disconnecting it.

3. Persons switching on remotely controlled machines shall take adequate precautions to

ensure that there is no one checking or working on the machine. To this end, a suitable

notice shall be affixed to the remote start equipment.

4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes,

vapors or particles.

5. Never operate the machine below or in excess of its limit ratings.

6. Keep all bodywork closed during operation. Bodywork should be opened for short periods

only, e.g. to carry out routine checks. Wear ear protectors when removing a panel.

7. People staying in environments or rooms where the sound pressure level reaches or

exceeds 90 dB(A) shall wear ear protectors.

8. Periodically check that:

? All guards are in place and securely fastened

? All hoses and/or pipes inside the machine are in good condition, secure and not

rubbing

? There are no leaks

? All fasteners are tight

? All electrical leads are secure and in good order

? Safety valves and other pressure relief devices are not obstructed by dirt or paint

? Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in

good condition, free of wear or abuse

Instruction book

6 2920 7112 41

9. If warm cooling air from dryers is used in air heating systems, e.g. to warm up a working

area, take precautions against air pollution and possible contamination of the breathing air.

10. Do not remove any of, or tamper with, the sound dampening material.

11. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.

Every pressure vessel or auxiliary installed outside the machine to contain air above

atmospheric pressure shall be protected by a pressure relieving device or devices as

required.

12. Yearly inspect the air receiver. Minimum wall thickness as specified in the instruction book

must be respected. Local regulations remain applicable if they are more strict.

Also consult following safety precautions: Safety precautions during installation and Safety

precautions during maintenance or repair.

These precautions apply to machinery processing or consuming air or inert gas. Processing

of any other gas requires additional safety precautions typical to the application which are

not included herein.

Some precautions are general and cover several machine types and equipment; hence

some statements may not apply to your machine.

1.5 Safety precautions during maintenance or repair

Precautions during maintenance or repair

1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes,

etc.).

2. Use only the correct tools for maintenance and repair work.

3. Use only genuine spare parts.

4. All maintenance work shall only be undertaken when the machine has cooled down.

5. A warning sign bearing a legend such as "Work in progress - do not start" shall be attached

to the starting equipment.

6. Persons switching on remotely controlled machines shall take adequate precautions to

ensure that there is no one checking or working on the machine. To this end, a suitable

notice shall be affixed to the remote starting equipment.

7. Close the dryer air outlet valve before connecting or disconnecting a pipe.

8. Before removing any pressurized component, effectively isolate the machine from all

sources of pressure and relieve the entire system of pressure.

9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety

precautions against toxic vapours of cleaning liquids.

10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by

covering the parts and exposed openings with a clean cloth, paper or tape.

11. Never weld on, or in any way modify, pressure vessels.

12. Whenever there is an indication or any suspicion that an internal part of a machine is

overheated, the machine shall be stopped but no inspection covers shall be opened before

sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil

vapor when air is admitted.

13. Never use a light source with open flame for inspecting the interior of a machine, pressure

vessel, etc.

14. Make sure that no tools, loose parts or rags are left in or on the machine.

15. All regulating and safety devices shall be maintained with due care to ensure that they

function properly. They may not be put out of action.

Instruction book

2920 7112 41 7

16. Before clearing the machine for use after maintenance or overhaul, check that operating

pressures, temperatures and time settings are correct. Check that all control and shut-down

devices are fitted and that they function correctly.

17. Protect the motor, electrical and regulating components, etc. to prevent moisture from

entering them, e.g. when steam-cleaning.

18. Make sure that all sound-damping material and vibration dampers, e.g. damping material on

the bodywork, is in good condition. If damaged, replace it by genuine material from the

manufacturer to prevent the sound pressure level from increasing.

19. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate

bowls.

20. The following safety precautions are stressed when handling refrigerant:

? Never inhale refrigerant vapours. Check that the working area is adequately ventilated;

if required, use breathing protection.

? Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin

with water. If liquid refrigerant contacts the skin through clothing, never tear off or

remove the latter; flush abundantly with fresh water over the clothing until all refrigerant

is flushed away; then seek medical first aid.

21. The following safety precautions are stressed when handling desiccant:

? Take precautions not to inhale desiccant dust.

? Check that the working area is adequately ventilated; if required, use breathing

protection.

? Do not overfill the dryer when replacing desiccant.

Also consult following safety precautions: Safety precautions during installation and Safety

precautions during operation.

These precautions apply to machinery processing or consuming air or inert gas. Processing

of any other gas requires additional safety precautions typical to the application which are

not included herein.

Some precautions are general and cover several machine types and equipment; hence

some statements may not apply to your machine.

1.6 Dismantling and disposal

Dismantling

Once the end of life of the machine is reached, please follow next steps:

1. Stop the machine.

2. Check all safety precautions mentioned in the previous chapters to secure safe handling

(e.g. LOTO, cool-down, depressurize, discharge, ...).

3. Separate the harmful from the safe components (e.g. drain oil from oil containing parts).

4. Refer to the disposal topic mentioned below.

Disposal of electrical and electronic appliances (WEEE)

This equipment falls under the provisions of the European Directive 2012/19/EU on waste

electrical and electronic appliances (WEEE) and may not be disposed as unsorted waste.

Instruction book

8 2920 7112 41

The equipment is labelled in accordance with the European Directive 2012/19/EU with the

crossed-out wheelie bin symbol.

At the end of life-time of the electric and electronic equipment (EEE) it must be taken to separate

collection.

For more information check with your local waste authority, customer center or distributor.

Disposal of other used material

Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts,

etc.) must be disposed of in an environmentally friendly and safe manner, and in line with the

local recommendations and environmental legislation.

Instruction book

2920 7112 41 9

2 General description

2.1 Introduction

General views

FX 1 up to FX 5

Instruction book

10 2920 7112 41

FX 6 up to FX 7

Introduction

The FX air dryers remove moisture from compressed air by cooling the air to near freezing point.

This causes water to condense. The condensate is automatically drained. The air is warmed up

before leaving the dryer.

Instruction book

2920 7112 41 11

2.2 Air system

Air flow diagram

Reference Name

4 Evaporator

5 Condensate separator

6 Impurity trap

10 Heat exchanger

11 Digital controller

13 Condensate drain

Description

Compressed air enters heat exchanger (10) and is cooled by the outgoing, cold, dried air. Water

in the incoming air starts to condense. The air then flows through heat exchanger/evaporator (10

and 4) where the refrigerant evaporates, causing the air to be cooled further to close to the

evaporating temperature of the refrigerant. More water in the air condenses. The cold air then

flows through separator (5) where all the condensate is separated from the air. The condensate

is automatically drained in the condensate drain.

The cold, dried air flows through heat exchanger (10) where it is warmed up by the incoming air

to approximately 10?C (18?F) below the incoming air temperature.

Condensation in the air net cannot occur unless the air is cooled to below the pressure dewpoint,

indicated by the digital controller (11).

Instruction book

12 2920 7112 41

2.3 Refrigeration system

Refrigerant flow diagram

Reference Name

1 Refrigerant compressor

2 Condenser

4 Evaporator

7 Expansion capillary tube

8 Refrigerant filter

Description

Compressor (1) delivers hot, high-pressure refrigerant gas which flows through condenser (2)

where most of the refrigerant condenses.

The liquid flows through the refrigerant dryer/filter (8) to capillary tube (7). The refrigerant leaves

the capillary tube at evaporating pressure.

The refrigerant enters evaporator (4) where it withdraws heat from the compressed air by further

evaporation at constant pressure. The heated refrigerant leaves the evaporator and flows through

the liquid separator (9) back to the compressor (1).

2.4 Automatic regulation system

Instruction book

2920 7112 41 13

Reference Name

3 Cooling fan

9 Hot gas bypass valve

Description

The condenser pressure must be kept as constant as possible to obtain stable operation. Fan

control switch therefore stops and starts the cooling fan (3).

If, under partial or no load, the evaporator pressure drops below a certain level, the hot gas

bypass valve opens and hot, high-pressure gas is fed to the evaporator circuit to prevent the

evaporator pressure from dropping any further.

2.5 Electrical system

Description

The fan control switch starts the fan motor as soon as the condenser pressure reaches the upper

set point of the switch and will stop the fan motor when the condenser pressure decreases to its

lower set point.

Instruction book

14 2920 7112 41

3 Installation

3.1 Dimension drawings

The dimension drawings can be found on the CD-ROM, delivered with the dryer.

Dimension drawing Model

2202 7549 00 FX 1 up to FX 5

2202 7463 00

9828 0837 37

FX 6 (up to ITJ 171 402) and FX 7 (up to ITJ 169 435)

FX 6 (from ITJ 171 402) and FX 7 (from ITJ 169 435)

Text on drawings Translation or explanation

Electric cable outlet Outlet for electric cable

Condensate pipe drain outlet Outlet for condensate drain hose or pipe

Air inlet Air inlet

Air outlet Air outlet

Air flow Air flow direction

Bushings UL version only Bushings (UL certification version only)

Female Female connection

Male Male connection

All dimensions: mm / inch All dimensions are in mm or inch as indicated on the

drawing

3.2 Installation proposal

Moving

Use a suitable tool (pallet carrier, fork lift truck) to move the dryer.

Do not use metal cables for lifting.

Move the dryer gently.

Instruction book

2920 7112 41 15

Example of compressor/dryer room

Installation proposal for FX 1 up to FX 5

Installation proposal for FX 6 up to FX 7

Attention

The disconnector switch (1) and the fuses are not supplied with the machine.

Reference Description

- Install the refrigerant air dryer on a level floor, suitable for its weight.

Instruction book

16 2920 7112 41

Reference Description

- Install the dryer where the ambient air is as clean as possible and where the

temperature of the air will never exceed the limits. See Reference conditions and

limitations. Keep the ventilation gratings of the dryer free.

The recommended minimum distance between the top of the unit and the ceiling is 1.5

m (58.5 in).

The minimum distance between the wall and the back of the dryer must be 1.5 m (58.5

in).

Lay out the condensate drain hose via a funnel towards a drain collector to allow visual

inspection. The hose must slope downwards.

If the condensate drain has been fitted outside the dryer room where it may be exposed

to freezing temperatures, it must be insulated.

- The power cable must be connected by a qualified electrician.

Connect the dryer to the correct voltage; if necessary, check the unit data plate.

Check that the electrical installation corresponds to local codes. The dryer must be

earthed and protected against short circuits using an automatic cut-out device with a

differential device.

An isolating switch must be installed near the dryer.

- Connect the compressed air lines to the marked inlet and outlet pipes of the dryer (see

Dimension drawings). Provide an air inlet valve and outlet valve. If a bypass pipe and

valve are installed, the dryer can be serviced while it is bypassed.

1 Location of isolating switch and fuses.

2 Minimum distance 1.5 m (58.5 in).

? Please keep environmental conditions stable (temperature and humidity) in order to avoid

refrigerant compressor/fan overload and/or reduction of dryer performance.

Similar failures shall affect warranty reimbursements.

? Please ensure the appropriate composition of the air within the machine room:

? Clean with no damaging contaminants. (e.g. dust, fibres, fine sand)

? Free of explosive or chemically unstable gases or vapors.

? Free of acid/alkaline forming substances, particularly ammonia, chlorine or hydrogen

sulfide.

Similar failures shall affect warranty reimbursements.

? Please remember that we do not recommend the application of duct to extract air in

presence of axial fans.

? All refrigerant dryers shall be equipped with proper pre-filters as close as possible to the

dryer air inlet. The filters should be replaced once a year according to the service plan or

sooner in high humidity ambient conditions.

Instruction book

2920 7112 41 17

3.3 Pictographs

Pictographs

Reference Name

1 Warning, under tension

2 Warning, air not fit for breathing

3 Warning, high pressure

4 Warning, rotating fan

5 Warning, hot surface

6 Switch off the voltage and depressurize the dryer before maintenance or repair

Instruction book

18 2920 7112 41

4 Operating instructions

4.1 Warnings

Safety precautions

The operator must apply all relevant safety precautions, including those mentioned in this

manual.

Altitude operation

Consult your supplier if operating above 3000 m (9843 ft).

4.2 Dryer control panel

Description

FX 1 up to FX 7

Reference Name

1 Digital controller, used for:

1. pressure dewpoint indication (main function)

2. alarms information

3. maintenance interval scheduling

2 Dryer on/off switch

Instruction book

2920 7112 41 19

4.3 Digital dryer controller

Identification

Front panel of the controller

Reference Name

1 Alarm icon

2 Refrigerant compressor icon

3 Fan icon

4 PDP (dewpoint) temperature

5 Unit (°C or °F)

6 Alarm LED

7 Button to snooze or to reset the alarm (only for remote alarm function).

8 SET button

9 UP button

10 DOWN button

8+9 Back to previous screen

8+10 Menu

Icons

Icon Name Mode Function

Alarm Off No active alarms

On Probe failure alarm

High temperature or low

temperature alarm

Service alarm

Refrigerant compressor Off Dryer off

On Dryer on

Flashing + SE Maintenance warning

Flashing + L2 Dewpoint too low

Dryer is stopped

Instruction book

20 2920 7112 41

Icon Name Mode Function

Flashing + H3 Too high discharge

temperature of the

refrigerant compressor

(see further)

Dryer is stopped

Fan Off Fan off

Flashing Not applicable

On Fan on

Remote alarm function

Depending on the dryer model, the controller allows to remotely control a number of alarms. This

is managed by means of a free NC (Normally Closed) contact.

The contact opens in case of an alarm or when the dryer is switched off.

Refer to the table below to identify the availability of the function and refer to the related picture to

identify the physical location of the free contact.

Availability of the remote alarm function

Model Fault message availability

P1 P2 P3 L2 H2 H3

FX 1 to FX 3 no yes no yes yes no

FX 4 and FX 5 yes yes no yes yes no

FX 6 to FX 7 yes yes yes yes yes yes

Location of the free contact (1)

Instruction book

2920 7112 41 21

Fault messages

Flashing fault message Description Remedy

Fan control probe failure

(Only available on FX 4 to FX 7)

Replace the probe.

Dewpoint temperature probe failure Replace the probe.

Refrigerant compressor discharge

temperature probe failure

(Only available on FX 6 to FX 7 with

remote alarm function)

Replace the probe.

Pressure dewpoint too high Refer to the fault and remedies

section.

Pressure dewpoint too low Refer to the fault and remedies

section.

Refrigerant compressor discharge

temperature too high; refrigerant

compressor stopped

(Only available on FX 6 to FX 7 with

remote alarm function)

Refer to the fault and remedies

section.

Condenser discharge temperature

too high

(Only available on FX 4 to FX 7)

Refer to the fault and remedies

section.

Condenser discharge temperature

too low

(Only available on FX 4 to FX 7)

Refer to the fault and remedies

section.

Instruction book

22 2920 7112 41

Flashing fault message Description Remedy

Internal EPROM error Reset by pressing one of the four

buttons.

If the problem persists, replace the

controller.

Maintenance required Perform the maintenance and reset

the alarm.

Resetting the maintenance warning

Front panel of the controller

To reset the maintenance warning, follow steps 1 to 12:

1. The display is flashing between standard view (dewpoint) and Maintenance required (SE)

alarm.

2. Push and hold buttons SET (8) and DOWN (10) to enter the menu.

3. Message “SE” appears on display.

4. Push and release the UP button (9).

5. Message “rS” appears on display.

6. Push and release the SET button (8).

7. Message “n” appears on display.

Instruction book

2920 7112 41 23

8. Push and release the UP button (9).

9. Message “y” appears on display.

10. Push and release SET (8) to reset service alarm.

11. Message “y” blinks for 3 seconds.

12. Then “rL” is fixed and “°C” blinks on display for about 10 seconds.

The service alarm is now reset.

Setting the service interval

To set the service interval, follow steps 1 to 9:

1. PDP is showing standard view.

2. Push and hold buttons SET (8) and DOWN (10) to enter the menu.

3. Message “SE” appears on display.

4. Push and release SET (8) to enter the “SE” menu.

5. Current service interval is displayed.

(“60” or any other value between “0” and “99”)

6. Select desired service interval using the UP or DOWN button.

Instruction book

24 2920 7112 41

(40=4000h, 55=5500h, 80=8000h,…)

7. Push and release SET to confirm the new service interval.

8. The selected value blinks during 3 seconds.

9. Then “rS” is fixed and “°C” blinks on display for ~10 seconds.

The new service interval is now set.

Freeze protection function (available with Remote Alarm function on FX 6 to FX 7)

Once the digital controller detects a dewpoint temperature below -2°C (28.4°F) during more than

2 minutes, (L2 Alarm), it switches off the refrigerant compressor.

Resetting the dryer after a refrigerant compressor stop (available with Remote Alarm function on

FX 6 to FX 7)

Before restarting the dryer it is necessary to identify the root cause. Alarms indicate

possible failures so it is necessary to contact your customer center.

Restarting the dryer without a deep investigation on possible root cause will affect the

reliability of the dryer and overrule the warranty reimbursement.

Press button 7 to reset the alarm.

The dryer restarts when both the following conditions are true:

? The dewpoint temperature is higher than -2°C (28.4°F).

? 30 seconds are passed from the refrigerant compressor stop (minimum balancing pressure

stop time). A countdown is available if the reset is made before the minimum stop time.

Silent alarm function (available with Remote Alarm function on FX 6 to FX 7)

To snooze the alarm, press button 7.

Instruction book

2920 7112 41 25

4.4 Starting

Attention

To ensure optimum operational efficiency, do not use dryer on/off switch repeatedly

within a short time period.

Wait at least 5 minutes to start the dryer again after stopping to allow pressure

equalization.

To keep the compressed air net free of condensate, start the dryer before starting the

compressor and stop the compressor before stopping the dryer.

Procedure

FX 1 up to FX 7

Step Action

1 If installed, close the dryer by-pass valve. See Installation proposal.

2 Press dryer on/off switch (2).

3 Open dryer air inlet valve (customer''s installation).

4 Approx. 5 minutes later, open dryer air outlet valve (customer''s installation).

5 Approx. 10 minutes later, the nominal dewpoint will be reached.

Instruction book

26 2920 7112 41

4.5 During operation

Procedure

FX 1 up to FX 7

Regularly check:

? The pressure dewpoint on the digital controller (1). The pressure dewpoint will deviate from

nominal if the air inlet conditions or volume flow differ from nominal.

? That condensate is discharged via condensate outlet. The amount depends on the operating

conditions.

4.6 Stopping

Attention

To ensure optimum operational efficiency, do not use dryer on/off switch repeatedly

within a short time period.

Wait at least 5 minutes to start the dryer again after stopping to allow pressure

equalization.

To keep the compressed air net free of condensate, start the dryer before starting the

compressor and stop the compressor before stopping the dryer.

Instruction book

2920 7112 41 27

Procedure

FX 1 up to FX 7

Step Action

1 Close the dryer inlet and outlet valve (customer’s installation).

2 Press dryer on/off switch (2), the dryer stops.

3 If provided, open the dryer by-pass valve.

Instruction book

28 2920 7112 41

5 Maintenance instructions

Safety precautions

Before starting any maintenance or repair work, close the air inlet and outlet valve and switch off

the voltage.

When removing the side panels of the dryer, be aware that internal elements such as the pipes

can be hot. Therefore, wait until the dryer has cooled down before removing the side panels.

Dryers of FX type contain refrigerant HFC.

When handling refrigerant, all applicable safety precautions must be observed. Please be

aware of the following points:

? Contact of refrigerant with the skin will cause freezing. Special gloves must be worn. In case

of contact with the skin, the skin should be rinsed with water. On no account may clothing be

removed.

? Fluid refrigerant will also cause freezing of the eyes; safety glasses must hence be worn.

? Refrigerant is hazardous. Do not inhale refrigerant vapours. Check that the working area is

adequately ventilated.

Local legislation

Local legislation may stipulate that:

? Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its

function must be undertaken by an authorised control body.

? The installation is checked once a year by an authorised control body.

Instructions

? Keep the dryer clean.

? Inspect and clean the filter of the automatic condensate drain monthly, in dusty environment

drain weekly:

? Release the pressure in the dryer by pressing the TEST push button on top of the

condensate drain (before switching off the supply voltage).

? Switch off the voltage

? Remove the filter from the automatic drain and clean it with an air jet, working from

inside to outside

? Reinstall the filter

? Brush or blow off the finned surface of the condenser monthly. Do not use water or solvents.

? Apply the drain wear kit once per year (see Spare Parts list for part number).

These maintenance intervals are intended for well ventilated, non-humid and not dusty

environments.

For particularly high humidity ambient conditions, the intervals should be halved.

Instruction book

2920 7112 41 29

Preventive maintenance schedule

Weekly

(In dusty environments)

Clean the filter of the automatic condensate drain.

Monthly Brush or blow off the finned surface of the condenser.

Clean the filter of the automatic condensate drain.

Yearly / Every 4000 hours

(Whichever comes first)

Replace drain kit (2200 9020 17)

Instruction book

30 2920 7112 41

6 Device settings

Regulating and safety devices

The regulating and safety devices are factory-adjusted to obtain optimum performance of the

dryer. Do not alter the setting of any of the devices.

Instruction book

2920 7112 41 31

7 Problem solving

Condensate drain and air inlet and outlet valves

FX 1 up to FX 5

FX 6 (up to ITJ 171 402) and FX 7 (up to ITJ 169 435)

FX 6 (from ITJ 171 402) and FX 7 (from ITJ 169 435)

Instruction book

32 2920 7112 41

Reference Name

1 Inlet and outlet valves

2 Condensate drain

3 Dryer on/ off switch

4 Isolating switch

Attention

Use only authorised parts. Any damage or malfunction caused by the use of

unauthorised parts is not covered by Warranty or Product Liability.

Apply all relevant safety precautions.

Before carrying out any maintenance or repair work on the dryer:

Close air inlet and outlet valves (1) of the dryer.

Move dryer on/off switch (3) to position 0 to switch off the voltage. See section Stopping.

Open the isolating switch (4) to prevent an accidental start.

The air inlet and outlet valves (1) can be locked during maintenance or repair

work as follows:

? Close the valve.

? Using a wrench, remove the screw fixing the handle.

? Lift the handle and turn it until the slot of the handle fits over the blocking edge on

the valve body.

? Fit the screw.

Faults and remedies

Condition Fault Remedy

1 Pressure dewpoint too high Air inlet temperature too high Check and correct; if necessary,

install a pre-cooler

Ambient temperature too high Check and correct; if necessary,

draw cooling air via a duct from a

cooler place or relocate the dryer

Air inlet pressure too low Increase inlet pressure

Adjust the pressure switch

Dryer capacity exceeded Reduce air flow

Shortage of refrigerant Have circuit checked for leaks and

recharged

Refrigerant compressor does

not run

See 3

Evaporator pressure too high See 5

Condenser pressure too high See 2

2 Condenser temperature too

high or too low

Fan or fan motor out of order Check fan/fan motor

Ambient temperature too high Check and correct; if necessary,

draw cooling air via a duct from a

cooler room or relocate the dryer

Condenser externally clogged Clean condenser

Instruction book

2920 7112 41 33

Condition Fault Remedy

3 Compressor stops or does not

start

Electric power supply to

compressor is interrupted

Check and correct as necessary

Thermal protection of

refrigerant compressor motor

has tripped

Reset the thermostatic protection

Restart of the dryer has been

too fast, not enough time for

pressure balancing

Wait a few minutes and restart

4 The condensate drain

remains inoperative

Drain system clogged

(blue LED on)

Have system inspected

(See section Maintenance

instructions for filter cleaning

procedure.

5 Evaporator pressure is too

high or too low at unload

Hot gas by-pass valve

incorrectly set or out of order

Have hot gas by-pass valve adjusted

Condenser pressure too high

or too low

See 2

Shortage of refrigerant Have circuit checked for leaks and

recharged

Instruction book

34 2920 7112 41

8 Technical data

8.1 Reference conditions and limitations

Reference conditions

Unit

Compressed air inlet pressure bar(e) 7

Compressed air inlet pressure psig 101.53

Compressed air inlet temperature ?C 35

Compressed air inlet temperature °F 95

Ambient temperature °C 25

Ambient temperature °F 77

Dewpoint °C 5

Dewpoint °F 41

Limits

Unit

Maximum compressed air inlet pressure

For FX 1 – FX 5

bar(e) 16

Maximum compressed air inlet pressure

For FX 1 – FX 5

psig 232.1

Maximum compressed air inlet pressure

For FX 6 (up to ITJ 171 402) and FX 7 (up to ITJ 169 435)

bar(e) 13

Maximum compressed air inlet pressure

For FX 6 (up to ITJ 171 402) and FX 7 (up to ITJ 169 435)

psig 188.5

Maximum compressed air inlet pressure

FX 6 (from ITJ 171 402) and FX 7 (from ITJ 169 435)

bar(e) 14

Maximum compressed air inlet pressure

FX 6 (from ITJ 171 402) and FX 7 (from ITJ 169 435)

psig 203.1

Minimum ambient temperature °C 5

Minimum ambient temperature °F 41

Maximum ambient temperature °C 43

Maximum ambient temperature °F 110

Maximum compressed air inlet temperature °C 55

Maximum compressed air inlet temperature °F 122

Instruction book

2920 7112 41 35

8.2 Air dryer data

FX 1 up to FX 5 - 115 V

Air dryer type Unit FX 1 FX 2 FX 3 FX 4 FX 5

Nominal power W 159 159 193 301 383

Nominal power hp 0.21 0.21 0.26 0.40 0.51

Electric power input, compressor W 130 130 164 268 350

Electric power input, compressor hp 0.174 0.174 0.220 0.359 0.469

Electric power input, fan motor W 29 29 29 33 33

Electric power input, fan motor hp 0.039 0.039 0.039 0.044 0.044

Weight of the unit kg 19 19 20 25 27

Weight of the unit lb 41.9 41.9 44.1 55.1 59.5

Refrigerant R134a R134a R134a R134a R134a

Total charge (approx.) kg 0.160 0.180 0.290 0.350 0.470

Total charge (approx.) lb 0.35 0.40 0.64 0.77 1.03

FX 1 up to FX 5 - 230 V 50 Hz

Air dryer type Unit FX 1 FX 2 FX 3 FX 4 FX 5

Nominal power W 130 164 190 266 284

Nominal power hp 0.17 0.22 0.25 0.36 0.38

Electric power input, compressor W 101 135 161 233 251

Electric power input, compressor hp 0.135 0.181 0.216 0.312 0.337

Electric power input, fan motor W 29 29 29 33 33

Electric power input, fan motor hp 0.039 0.039 0.039 0.044 0.044

Weight of the unit kg 19 19 20 25 27

Weight of the unit lb 41.9 41.9 44.1 55.1 59.5

Refrigerant R134a R134a R134a R134a R134a

Total charge (approx.) kg 0.150 0.170 0.290 0.350 0.480

Total charge (approx.) lb 0.33 0.37 0.64 0.77 1.06

FX 1 up to FX 5 - 230 V 60 Hz

Air dryer type Unit FX 1 FX 2 FX 3 FX 4 FX 5

Nominal power W 170 170 220 310 360

Nominal power hp 0.23 0.23 0.30 0.42 0.48

Electric power input, compressor W 140 140 190 270 327

Electric power input, compressor hp 0.19 0.19 0.26 0.36 0.44

Electric power input, fan motor W 29 29 29 33 33

Electric power input, fan motor hp 0.039 0.039 0.039 0.044 0.044

Weight of the unit kg 19 19 20 25 27

Instruction book

36 2920 7112 41

Air dryer type Unit FX 1 FX 2 FX 3 FX 4 FX 5

Weight of the unit lb 41.9 41.9 44.1 55.1 59.5

Refrigerant R134a R134a R134a R134a R134a

Total charge (approx.) kg 0.160 0.170 0.28 0.350 0.450

Total charge (approx.) lb 0.35 0.37 0.62 0.77 0.99

FX 6 (up to ITJ 171 402) - FX 7 (up to ITJ 169 435) - 115 V

Air dryer type Unit FX 6 FX 7

Nominal power (at reference

ambient temperature)

kW 0.54 0.67

Nominal power (at reference

ambient temperature)

hp 0.72 0.90

Nominal power (at maximum

ambient temperature)

kW 0.79 0.91

Nominal power (at maximum

ambient temperature)

hp 1.06 1.22

Electric power input. fan motor kW 0.057 0.057

Electric power input. fan motor hp 0.076 0.076

Weight of the unit kg 51 51

Weight of the unit lb 112.2 112.2

Refrigerant R404a R404a

Total charge (approx.) kg 0.4 0.4

Total charge (approx.) lb 0.88 0.88

FX 6 (up to ITJ 171 402) - FX 7 (up to ITJ 169 435) - 230 V 50 Hz

Air dryer type Unit FX 6 FX 7

Electric power input W 609 673

Electric power input hp 0.817 0.902

Electric power input, compressor W 544 608

Electric power input, compressor hp 0.730 0.815

Electric power input, fan motor W 65 65

Electric power input, fan motor hp 0.087 0.087

Weight of the unit kg 44 44

Weight of the unit lb 97 97

Refrigerant R404A R404A

Total charge (approx.) kg 0.400 0.400

Total charge (approx.) lb 0.882 0.882

From ITJ 125 139 to ITJ 169 435 dryers are equipped with refrigerant R452A. Other technical

data reported in the table remain valid.

Instruction book

2920 7112 41 37

FX 6 (up to ITJ 171 402) - FX 7 (up to ITJ 169 435) - 230 V 60 Hz

Air dryer type Unit FX 6 FX 7

Electric power input W 629 777.5

Electric power input hp 0.843 1.043

Electric power input, compressor W 572 720.5

Electric power input, compressor hp 0.767 0.966

Electric power input, fan motor W 57 57

Electric power input, fan motor hp 0.076 0.076

Weight of the unit kg 44 44

Weight of the unit lb 97 97

Refrigerant R404A R404A

Total charge (approx.) kg 0.400 0.400

Total charge (approx.) lb 0.882 0.882

FX 6 (from ITJ 171 402) - FX 7 (from ITJ 169 435) - 115 V

Air dryer type Unit FX 6 FX 7

Nominal power (at reference

ambient temperature)

kW 0.673 0.717

Nominal power (at reference

ambient temperature)

hp 0.902 0.961

Nominal power (at maximum

ambient temperature)

kW 1.1 1.177

Nominal power (at maximum

ambient temperature)

hp 1.475 1.578

Electric power input. fan motor kW 0.057 0.057

Electric power input. fan motor hp 0.076 0.076

Weight of the unit kg 44 44

Weight of the unit lb 97 97

Refrigerant R134a R134a

Total charge (approx.) kg 0.33 0.3

Total charge (approx.) lb 0.726 0.66

FX 6 (from ITJ 171 402) - FX 7 (from ITJ 169 435) - 230 V 50 Hz

Air dryer type Unit FX 6 FX 7

Nominal power (at reference

ambient temperature)

kW 0.674 0.716

Nominal power (at reference

ambient temperature)

hp 0.903 0.96

Nominal power (at maximum

ambient temperature)

kW 0.955 1.104

Nominal power (at maximum

ambient temperature)

hp 1.28 1.48

Instruction book

38 2920 7112 41

Air dryer type Unit FX 6 FX 7

Electric power input. fan motor kW 0.065 0.065

Electric power input. fan motor hp 0.087 0.087

Weight of the unit kg 44 44

Weight of the unit lb 97 97

Refrigerant R134a R134a

Total charge (approx.) kg 0.33 0.3

Total charge (approx.) lb 0.726 0.66

FX 6 (from ITJ 171 402) - FX 7 (from ITJ 169 435) - 230 V 60 Hz

Air dryer type Unit FX 6 FX 7

Nominal power (at reference

ambient temperature)

kW 0.726 0.763

Nominal power (at reference

ambient temperature)

hp 0.973 1.023

Nominal power (at maximum

ambient temperature)

kW 1.068 1.067

Nominal power (at maximum

ambient temperature)

hp 1.432 1.43

Electric power input. fan motor kW 0.057 0.057

Electric power input. fan motor hp 0.076 0.076

Weight of the unit kg 44 44

Weight of the unit lb 97 97

Refrigerant R134a R134a

Total charge (approx.) kg 0.33 0.3

Total charge (approx.) lb 0.726 0.66

Instruction book

2920 7112 41 39

9 Pressure equipment directives

Components subject to Pressure Equipment Directive

All pressure bearing components are designed category I or less according to European Directive

97/23/EC (until 19/07/2016) or Directive 2014/68/EU (from 20/07/2016 onwards).

Instruction book

40 2920 7112 41

10 Declaration of conformity

Typical example of a Declaration of Conformity document

(1): Contact address:

Atlas Copco Airpower n.v.

P.O. Box 100

B-2610 Wilrijk (Antwerp)

Belgium

(2): Applicable directives

(3): Standards used

On the Declaration of Conformity / Declaration by the Manufacturer, the harmonized and/or other

standards that have been used for the design are shown and/or referred to.

The Declaration of Conformity / Declaration by the Manufacturer is part of the documentation that

is supplied with this device.

Instruction book

2920 7112 41 41





COMMITED TO SUSTAINABLE PRODUCTIVITY

We stand by our responsibilities towards our customers, towards the

environment and the people around us. We make performance stand

the test of time. This is what we call — Sustainable Productivity.

www.atlascopco.com

No. 2920 7112 41 / 2018 - 10 - Printed in Belgium Atlas Copco Airpower NV. All rights reserved. Designs and specifications are subject to change without notice or obligation.

献花(0)
+1
(本文系wangweiqin1...首藏)