CC1N7161de

06.06.2002

Siemens Building Technologies

HVAC Products

ISO 9001

7

161

Oil Burner Controls LAE1...

Series 02

supplementary Data Sheet 7713

Oil burner controls for use with burners of any capacity in intermittent operation.

For safety reasons, at least one controlled shutdown must take place every 24

hours.

The LAE1... and this Data Sheet are intended for use by OEMs which integrate the

burner controls in their products.

Use

The LAE1... with the associated flame detector RAR7 or RAR8 is used for the fully

automatic startup and supervision of

- single-stage forced draft burners

- multistage forced draft burners

- modulating forced draft burners

- with any oil throughput

The LAE1... oil burner controls are tested and certified to EN 230.

The design, control sequence and setting choices offered by the LAE1... enable this

burner control to be used in almost any type and size of oil-fired combustion plant.

2/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

- Prepurge time adjustable between 8 and 63 seconds

- Operation with or without postpurge (optional)

- Fully automatic control of air damper, if required (with any actuator running time)

- Possibility of air check, in connection with a functional check of the air pressure

switch prior to startup

- Ignition (optional, either directly or with pilot burner)

- Preignition time adjustable (?long? - during prepurge, ?short? - 3 seconds)

- Safety time adjustable between 0 and 9 seconds

- Operation without or with one-time start repetition in the event of loss of flame dur-

ing operation

- Automatic extraneous light test during burner off periods and during the pre- and

postpurge time

- Integrated lockout warning lamp

- Electric remote reset

- Cover with 2 additional sealing screws to ensure protection against tampering (re-

fer to ?Dimensions?)

Warning notes

To avoid injury persons, damage to property or the environment, the following

warning notes should be observed!

The unit may only be opened, interfered with or modified by qualified staff!

g183 Before performing any wiring changes in the connection area of the LAE1..., com-

pletely isolate the unit from the mains supply (all-polar disconnection)

g183 Ensure protection against electric shock hazard by providing adequate protection

for the burner control’s connection terminals

g183 Check wiring and all safety functions prior to commissioning and each time a fuse

has been replaced

g183 Press the lockout reset button only manually, without using any tools or pointed

objects

g183 Fall or shock can adversely affect the safety functions. Such unit may not be put

into operation, even if they do not exhibit any damage

g183 Do not press the lockout reset button on the unit or the remote lockout reset button

for more than 10 seconds since this would damage the lockout relay in the unit

Mounting notes

g183 Ensure that the relevant national safety regulations are complied with

g183 Mount and adjust the flame detector such that it can detect the flame

Installation notes

g183 Installation work must be carried out by qualified staff

g183 Live and neutral conductors may not be mixed up

g183 For the connection of valves and other plant components, use the plant diagram

and the mounting and commissioning instructions provided by the burner manu-

facturer

g183 In the event of loss of flame during operation, the burner control will initiate lockout.

If start repetition is required, changeover latch ?UL3? must be set to ?Repetition?

Specific features

3/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Electrical connection of flame detectors

It is important to achieve practically disturbance- and loss-free signal transmission:

g183 Never run the detector cable together with other cables

– Line capacitance reduces the magnitude of the flame signal

– Use a separate cable

g183 Observe the maximum permissible detector cable lengths (refer to ?Technical

data?)

Commissioning notes

g183 Commissioning and maintenance work must be carried out by qualified staff

g183 When commissioning the plant or when doing maintenance work, make the follow-

ing safety checks:

Safety check to be carried out Anticipated response

a) Burner start with flame detector darkened Lockout at the end of ?TSA?

b) Burner start with flame detector exposed

to extraneous light

Lockout after no more than 40

seconds

c) Burner operation with simulated loss of

flame; for that purpose, darken the flame

detector in operation and maintain that

state

- With repetition: Restart fol-

lowed by lockout at the end of

?TSA?

- Without repetition: Immediate

lockout

Norms and standards

CE conformity according to the directives of the European Union

- Electromagnetic compatibility EMC 89 / 336 EEC

- Low voltage directive 73 / 23 EEC

Service notes

g183 Check wiring and all safety functions each time a unit has been replaced

Disposal notes

The unit contains electrical and electronic components and may not be disposed of

together with household garbage.

Local and currently valid legislation must be observed.

4/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Mechanical design

- For mounting on the burner, in control panels or on panel fronts

- Housing and plug-in base are made of impact-proof and flame-retarding plastic

- Unit of plug-in design, secured to the base with 4 screws

- Large wiring compartment inside the plug-in base

- Unit fuse to protect the control contacts against overloads

- Robust printed circuit board with

– sequence switch driven by a synchronous motor

– auxiliary relay

– electronic detector current amplifier

– switching, control and setting elements

Type summary and ordering

Factory settingsType reference / ordering

(type reference is given inside the housing near the contacts)

Mains voltage

Hz t1 TSA t9

LAE1/1355 AC 220...240 V 50 30 s 5 s 5 s

LAE1/8846 AC 220...240 V 50 30 s 2 s 2 s

LAE1/8863 AC 100...110 V 50 30 s 2 s 2 s

LAE1/8864 AC 100...110 V 60 30 s 2 s 2 s

LAE1/8865 AC 220...240 V 60 30 s 2 s 2 s

LAE1.1/8847 AC 220...240 V 50 15 s 2 s 2 s

LAE1... oil burner controls are supplied without terminal base.

Accessories

Terminal base AGG41041713 (AE)

- To be ordered as a separate item

- For Pg 11

Terminal base AGG11.1

- To be ordered as a separate item

- For M16 x 1.5

Flame detector RAR7 / RAR8 refer to Data Sheet 7713

g70

5/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Technical data

Mains voltage AC 220 V –15 %...AC 240 V +10 %

AC 100 V –15 %...AC 110 V +10 %

Mains frequency 50 Hz ±6 %

Primary fuse (externally) max. 10 A (slow)

Degree of protection IP 40

Mounting position optional

Cable glands Pg 11 or BSP ?“

Weight approx. 1.85 kg

Unit fuse (integrated) T6,3H250V to DIN EN 60 127

Power consumption

- On startup

- In operation

9 VA

6 VA

Max. perm. load on control outputs

- Per terminal

- Total (input current terminal 1)

4 A to VDE 0660 AC3

5 A to VDE 0660 AC3

Transport DIN EN 60 721-3-2

Climatic conditions class 2K2

Mechanical conditions class 2M2

Temperature range -20...+60 °C

Humidity < 95 % r.h.

Operation DIN EN 60 721-3-3

Climatic conditions class 3K5

Mechanical conditions class 3M2

Temperature range -20...+60 °C

Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

Refer to Data Sheet 7713!

Perm. length of connecting cable

(in the case of longer distances, use low-

capacitance cable, e.g. single-core, and

flame detector RAR8 )

20 m

Required detector current min. 8 μA

Possible detector current max. 25 μA

RAR...

+

-

M

- +

14 13 LAE1...

7161v01/1098

Legend

RAR... Flame detector

M Microammeter

General unit data

Environmental

conditions

Flame detectors

Measurement circuit

for LAE1...

6/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Function

The burner will be started only if

- the sequence switch of the LAE1... is in its start position

- the LAE1... has not triggered lockout

- the contacts of all control and monitoring devices in the control loop between ter-

minals 8 and 9 are closed

- the air pressure switch – if included in the test circuit – does not signal air pressure

Faults in the flame supervision section of the LAE1... prevent startup or, in the case of

startup, lead to lockout.

If the air damper is not controlled by the LAE1..., terminals 20, 21 and 22 must be inter-

connected.

The LAE1... can control the following burner plant components:

- Fan motor

- Flue gas fan

- Air damper

- Ignition transformer

- 1 to 3 fuel valves

- 1 external fault indication unit

A load controller with 3-position output can be connected.

Specific features

- Continuous indication of the program sequence in the viewing window of the unit

cover

- In the event of fault, the program indicator shows the program phase during which

lockout occurred

- The motor of the sequence switch can be switched off to facilitate the burner set-

ting procedure

- The cam shaft can be rotated manually

... on startup

First, the fan motor is switched on via terminal 3 and the actuator is controlled via ter-

minal 22. When the air damper reaches its maximum position, the sequence switch of

the LAE1... starts to operate and the prepurge time commences. The minimum air

pressure set on the air pressure switch must then be reached within 10 seconds (or

within 7 seconds in the case of operation with postpurge) and be maintained until con-

trolled shutdown occurs. Otherwise, the burner control will initiate lockout. A flame sig-

nal during the prepurge time also leads to lockout. On completion of the adjusted pre-

purge time, the air damper is given the control command to return to the minimum posi-

tion. During the time the air damper is closed, the sequence switch does not operate.

As soon as the signal contact for the minimum throttling setting is actuated by the ac-

tuator, the sequence switch starts again and controls the program sequence which can

no longer be influenced from outside:

- Preignition (if the ignition equipment was not already switched on during the pre-

purge time)

- Release of the first fuel valve connected to terminal 5 (the fuel valve of a pilot

burner which, on completion of the second safety time must be switched off, is to

be connected to terminal 10, however)

- Completion of the adjusted safety time. If, during this period of time, no flame is

established, the burner control will initiate lockout with interlocking

- 11 seconds after release of the first fuel valve, the second fuel valve will be re-

leased

- The pilot burner – if present and connected to terminal 10 – will be shut down

- The load controller will be switched on after another interval of 12 seconds, which

means that the burner’s operating position is now reached. From now on, the load

controller controls burner output by increasing or decreasing the oil throughput and

the amount of air, depending on the demand for heat

Preconditions for

burner startup

g70

Startup sequence

7/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

If the flame is lost during operation, the burner control will initiate lockout or – if operat-

ing mode ?with start repetition? is used – make a new start.

In that case, the sequence switch must return to its start position, however, and post-

purging will take place – if programmed.

... after a controlled shutdown

Controlled shutdown occurs as soon as a control or monitoring device in the control

loop between terminals 8 and 9 opens its contact.

The fuel valves are immediately shut and postpurging, if included, will start.

The sequence switch will return to its start position where it stays until the next switch

on command is given.

... after lockout of the LAE1...

After pressing the integrated or external lockout reset button, the sequence switch will

return to its start position, provided the fault has been corrected.

The only component of the burner plant that is switched on here is the fan motor con-

nected to terminal 17.

Since in normal circumstances, the control thermostat or pressurestat continues to call

for heat, the sequence switch initiates a new start after it has reached its start position.

Control sequence

8/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Program sequence indicator

LANDIS & GYR

Type Serie ts s

V~ c/s Hz VA

4A V~ 2A

3 5 6 7 10111720212

1 23

t1

A

B

C

E

F

G

= 8...63 s

(1)

7161p02/0102

40

30

The program sequence indicator shows the respective startup position.

The letters correspond to those given in the sequence switch diagram beside the

viewing window.

The numbers give the remaining prepurge time.

In the event of lockout, the sequence switch and the program sequence indicator stop,

thus indicating the operating phase during which lockout occurred.

E

F

7

1

61

p04

/0

1

02

40

30

716

1p

03

/0

10

2

Valve 2 connected to terminal 7

will be opened

Prepurge time lasts another 35 seconds

Two changeover latches on the underside of the burner control can be used to make

the following settings:

Long preignition time During prepurging Factory settingUL2

Short preignition time 3 seconds ---

With repetition In the event of loss of flame

during operation

---UL3

Without repetition In the event of loss of flame

during operation

Factory setting

The factory setting can only be changed after loosening the screw.

Retighten screw properly!

Reading the program

sequence indicator

Changing the

control sequence

g70

9/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Settings and adjustments on the burner control

g183 Loosen all 6 screws and remove the cover of the LAE1...

g183 Always start counting the switching cams from the motor side

g183 You can manually turn the cam shaft to any position you want

(clockwise rotation as seen from the motor)

UL1 N1 N2 N7 N8 PA

7

1

61p05/010

2

Setting elements

N1 Cam 1, fixed

N2 Cam 2, adjustable (safety time)

N3 Cam 3, adjustable (safety time)

N7 Cam 7, fixed

N8 Cam 8, adjustable (prepurge time)

PA Sequence position indicator

UL1 Operating switch ON / OFF

for sequence switch motor

On the underside of the base:

UL2 Changeover latch ?Short / long? preignition time

UL3 Changeover latch ?With / without? repetition

Adjusting the prepurge time ?t1?

- Loosen the fixing screw of the red cam N8

- Turn cam shaft manually until the required prepurge

time is indicated next to the index notch on the se-

quence switch carrier

- Hold the cam shaft firm and turn cam N8 until the

tappet operated by it trips, or until the cam stops at

this tappet

- Tighten the cam’s fixing screw carefully and then

check the adjusted time.

The adjusted time is also visible through the viewing

window when the LAE1... is in its start position

Adjustment of the mark of the red cam N8 to the gradua-

tion marks of the block cam N7 results in the prepurge

times given in the adjacent table.

g73 g73g73 g73g73g73 N7 N8

7161p06/0102

Adjustment to t1

Graduation mark I 8 s

Graduation mark II 18 s

Graduation mark III 28 s

At stop 63 s

Factory setting approx. 30 s

Adjusting the safety time ?TSA?

- Loosen the stop screws of cams N2 and N3

- Hold cam N1 firm and align the graduation mark of

cam N2 to the corresponding time marking of cam

N1 (intermediate positions possible) (see adjacent

illustration and table). Lock cam N2

- Set adjustment mark of cam N3 to the lowest stop of

cam N2 and lock cam N3

- Check the adjusted safety time and adjust the new

value on the rating plate of the cover

(adjustment slot on the underside of the cover)

III II I N1 N2

7161p07/0102

Adjustment to TSA

Graduation mark I 0 s

Graduation mark II 4.5 s

Graduation mark III 9 s

Factory setting g163 5 s

10/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Connection diagram

Unit fuse 6.3 A (slow) in the current path between terminal 1 and relay contact ?br...? is

not shown.

L

1

EK2

16

15

14

LF

+

13

12

L2

17

M2

M

~

11

OV3OV2

7105

(OV)OV1

Z

N

26

19 9 4

18 83

LP

P

W

R

T

T

N

M

~

~

LK

N

20

az

M1

2122

(11)

NTC

FR

XI

a

VIII

a

fr

2

IX

b

br1

VIII

b

ar1 ar3

EK1

XIII

ba

IX

a

IV

ab

XII

ab

IVII

UL2

b

IV

I

a

UL3

fr1

XI II

a

b

b

X

AR

br2

BR

III

V

b a

VI

SM

ar2

UL1

L1

7161a01/1098

SB

AR Load relay with contacts ?ar...? LP Air pressure switch

BR Lockout relay with contacts ?br...? M... Fan

EK1 Lockout reset button on the LAE1... NTC High temperature conductor (delay device)

(do not press ?EK1? for more than 10 seconds!) OV... Oil valve

EK2 Remote lockout reset button (OV) Fuel valve for a pilot burner, will be switched off on

(do not press ?EK2? for more than 10 seconds!) completion of the 2

nd

safety time

FR Flame relay with contacts ?fr...? R Control thermostat or pressurestat

L1 Fault indication lamp (integrated) SB Safety limit thermostat

L2 Fault indication lamp (external) SM Synchronous motor of sequence switch

LF Flame detector RAR... UL1 Operating switch for sequence switch motor

LK Air damper actuator with end or auxiliary switches (only accessible when cover is removed)

a = actuator travels to the ?fully open? position UL2 Changeover latch ?Long / short preignition time?

(max. air volume) UL3 Changeover latch ?With / without repetition?

z = actuator travels to the ?fully closed? position W Limit thermostat or pressure switch

(min. air volume) Z Ignition transformer

Legend

11/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Time diagram of sequence switch

The maximum permissible afterburn time is 7 seconds – from the start of ?t6?.

Customer-specific presettings of the times on request!

t3

t7

t10

t1

t11

t8

T

t12

t6

TSA

t4 t9

t3′ t5

3

63

66

70

93

86

67

89

79

81

a

b

a

b

a

b

a

b

a

b

a

b

a

b

a

b

a

b

I

II

III

IV

V

VI

VII

VIII

IX

X

XI

XII

XIII

7161d01/1098

T 120 s Cycle time of the sequence switch

TSA 0...9 s Adjustable first safety time

t1 8...63 s Adjustable prepurge time

t3 t1 + t11 + t12 + 7 s ?Long? preignition time

t3′ 3 s ?Short? preignition time

t4 11 s Interval between release of 1

st

and 2

nd

fuel valve

t5 12 s Interval between release of 2

nd

and 3

rd

fuel valve or

load controller

t6 T – (30 + t1) Postpurge time

t7 3 s Delay time

t8 t1 + 30 + t11 + t12 Total startup time

t9 5 s Second safety time (only with pilot burner)

t10 10 s Bridging time (predefined time for air control)

t11 optional Opening time for the air damper

t12 optional Closing time for the air damper

Legend

12/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Connection examples

Connection diagram and sequence program for operation with long preignition and

repetition (actuator control checked, no load control).

When using an air pressure switch LP, the connections between terminals 3 and 4

and 8 and 18 are not required

1 2 13 14 15 16 12 19 18 8 9 4 3 22 21 20 17 6 5 7 11

UL.3

UL.2

M1 M2

MM

c1

e1

L

c2

e2

H

N

+

LF

EK

2

L2

LPP

c1



W

R

T

T



e1

c1

1 2 12 11

a z

M

N LK

e2

d1

c2

Z

OV1

OV2

OV3

d1

d1

Repetition

Repetition

LAE1

7161a02/1098

SB



Luft

?l

M

LK

OV3

OV2

OV1

7161s01d/1095

Air damper control (in detail)

In the case of burners without air damper

or an air damper not controlled by the

LAE1..., terminals 20, 21 and 22 must be

interconnected.

In that case, current path 18-c1-21 must

not be present!

t11 t1 t12 t11 tn t6 t12

22

21

21/d1

18/c1/d1

20

LK"a"

LK"z"

A BCDE

7161d03/1095

AB

M

t8

t7

t11 t1 t12

TSA

t3

t4

t5

M1

M2

LK

Z

OV1

OV2

OV3

FW

L2

Kl.3

17

22/21

6

5

7

11

13/14

12

tn

C

t6

DE F

t8

GH

t6

t7

t1

TSA

t3

KL M

7161d02/1098

I

Legend

A Start G-H Operation

A-B Normal startup H Loss of flame

B-C Operation H-I Return to start position

C Controlled shutdown I Repetition

C-D Postpurging I-K Startup without establishment of flame

D-E Closing the air damper K-L Fault

E-F Burner off period L Reset

F Restart L-M Return to start position

F-G Startup M Restart

13/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Connection examples (cont’d)

Connection diagram and sequence program for operation with short preignition and without repetition.

Ignition of main burner with light oil pilot burner (on / off control with checked actuator control).

When using an air pressure switch LP, the connections between terminals 3 and

4 and 8 and 18 are not required

P

H

M1 M2

MM

c1

e1

c2

e2

L

1 2 12 13 14 15 16 17 18 8 9 4 3 22

N

L2

+

LF

EK2

c2

e2

c1/c2

LP



T

T

W

R1

c1

e1 c1

1

a

LK

100%

M

2

z

11 12 36

13 14

15 17

20 21 5610

BS

I

II III

IV

T

R2

d1

46%31%38%

16

N

0% 33%

4 5 78

(SQ...)

OV3

Z

(OV)

OV2

d1

UL.2

UL.3

Repetition

Repetition

711

7161a03/0202

LAE1

19

SB

?l

Luft

Leicht?l

OV3

OV2

M

LK

(OV)

7161s02d/1195

Control switch ?BS?

I High-flame

II Stop

III Low-flame

IV Automatic control

Air damper control (in detail) g174

AB CDE

18/c1

"a"

20

"kl.Fl."

"z"

t11 t1 t12 t11

7161d04/0998

22/c1

21/d1

21/d1/

BS/R2

M1

M2

LK

Z

(OV)

OV2

OV3

FW

L2

A B C D E F G H IK L

t6

t7

t1

TSA

t3′

t4

t5

t9

t8

t7

t11 t1 t12

t6

TSA

t3′

t4

t5

t9

Kl.3

17

22/21

6

10

7

11

13/14

12

7161d05/1098

M

Legend

A Start G-H Operation

A-B Normal startup H Loss of flame

B-C Operation H-I Fault

C Controlled shutdown I Reset

C-D Postpurging I-K Return to start position

D-E Closing the air damper K Restart

E-F Burner off period K-L Startup

F Restart L Operation

F-G Startup

14/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Connection examples (cont’d)

Connection diagram for modulating burner control with checked actuator control.

Burners designed for modulating burner control also use the devices of the temperature or pressure control loop, in

addition to the standard burner control equipment.

Example:

- One modulating controller with a 3-position output

- Temperature or pressure sensor QA... / QB...

- One actuator for the control of the air damper and oil throughput SQ...

- One auxiliary relay d1

- One control switch BS

- One oil volume controller RV

When using an air pressure switch LP, the connections between terminals 3 and

4 and 8 and 18 are not required

1 2 13 14 15 16 12 19 18 8 9 4 3 20 22 21

d1c1

e1

c1

c1

10 11 17 6 5 7

e2

c2

d1

Q...

c1/c2

H

M1 M2

MM

c1

e1

c2

e2

LN

LF

+

EK

2

L2

P

LP

T

T

W

R

M

a z

12

LK

11

12 N

RV

SQ...

Z

OV1



BS

I

II

III

IV

LAE1

7161a04/1098

SB



Luft

?l

M

OV1 RV

SQ

.

.

.

LK

7161s03d/1095

Control of semiautomatic operating mode

This operating mode is used when, for specific reasons, fully automatic

operation is not desired.

Example: Industrial burners

The burner is started by pressing button I (N.O.). Burner shutdown is

achieved either by pressing button 0 (N.C.) or when there is a response

from the limit thermostat.

18 8 9

L

N

I 0

DK

W

T

7161a05/1098

Air pressure switch LP

(Recommended for burners that use separate motors for the fan and the

fuel pump).

The air pressure is continuously monitored from burner startup through

controlled shutdown.

If 10 seconds after the start of prepurging, or 7 seconds with the pro-

gram with pre- and postpurging, the adjusted and required minimum air

pressure is not reached, or if the air pressure drops again, the burner

control will initiate lockout.

If air pressure switch LP is connected as shown in the adjacent diagram,

an automatic functional check is made prior to each start.

If the contact position is wrong, there will be no start.

(17)

3 4 8 9 18 19

e

M

c

ma

x

.

5

A

0,1 A

LP

P

T R

WT

N

~

7161a06/1098

M

15/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

AR Load relay with contacts ?ar...?

BR Lockout relay with contacts ?br...?

BS Control switch

c... Fan contactor with contacts ?c...?

d... Auxiliary relay with contacts ?d...?

DK Button

e... Thermal overcurrent release

EK1 Lockout reset button on the LAE1... (do not press ?EK1? for more than 10 s!)

EK2 Remote lockout reset button (do not press ?EK2? for more than 10 s!)

FR Flame relay with contacts ?fr...?

FW Flame supervision

H Main switch

L Lamp

L1 Fault indication lamp (integrated)

L2 Fault indication lamp (external)

LF Flame detector RAR...

LK Air damper actuator with end or auxiliary switches

a = actuator travels to the ?fully open? position (max. air volume)

z = actuator travels to the ?fully closed? position (min. air volume)

LP Air pressure switch

M... Fan

NTC High temperature conductor (delay device)

OV... Oil valve

(OV) Fuel valve for a pilot burner, will be switched off

on completion of the second safety time

R Control thermostat or pressurestat

RV Control valve

SB Safety limit thermostat

SM Synchronous motor of sequence switch

UL1 Operating switch for sequence switch motor

(only accessible when cover is removed)

UL2 Changeover latch for ?Long / short? preignition time

UL3 Changeover latch for ?With / without? repetition

W Limit thermostat or pressure switch

Z Ignition transformer

Legend

16/16

Siemens Building Technologies CC1N7161de

HVAC Products 06.06.2002

Dimensions

Dimensions in mm

1

17

116

2

PG11/3/4"-16DNF

A

210

B A

A B A

13

,5

14

,

5

25

25

14

0

4,5

SG

EK

17

,

2

18,

9

4,

5

17,

2

105

17,7

139

,

4

933333333

17,7 174

209,4

46

,

7

36

,

7

33

69

,

7

CC

C

7161m01/0202

LAE1...

AGG41041713 (AE)

1

17

11

6

2

M16 x 1,5

AGG11.1

LAE1...

To remove the LAE1... from its plug-in base, it is merely necessary to loosen the 4

screws ?A?.

To remove the unit cover, also loosen the 2 screws ?B?.

C Elongated holes for fixing the plug-in base

SG Viewing window

EK Lockout reset button

Legend